2.4 Requirements regarding installation location
(Detail from the instruction manual)
The system is designed for stationary use in an outdoor area. Make certain that the specified
environmental conditions are maintained at all times. Use in non-specified environments,
e.g. on board ships, in explosive atmospheres or at high altitude (see the climatic environmental
conditions) is prohibited.
CAUTION
Hazard due to condensation!
Condensation may form if the system has not had sufficient time to settle to the
environmental conditions following transport or before it is put into operation
again. (Connection to AC supply is required.)
2.4.1 Environmental conditions
Observe the environmental conditions information in the technical data (
2.4.2 Requirements regarding installation location
Please note that the battery system may not be set up and operated
•
in buildings, garages, courtyards and other covered structures
•
in areas where there is a risk of flooding
•
in areas where there is a risk of fire and explosion
•
in the vicinity of combustible materials
•
and in areas with sandstorms
•
in permanent residential areas
•
in the vicinity of escape routes
Installation conditions:
•
The "Commissioning requirements" checklist must be completed and signed
(
•
The system is only suitable for outdoor installation.
•
Observe the following floor space requirements for the system:
−
The floor space is to be constructed at the installation location in accordance with the local
conditions and technical data (
−
Wind-protected
−
The floor space is exactly horizontal.
−
Cable entry is from below.
−
The floor space has the required load capacity for the 1.25 t weight of the system and has
to withstand this load permanently.
If applicable, also take into account the weight of the means of transport.
−
Sufficient drainage is available.
•
Earthing via ring earth electrode for flexible connection cable (min. 16 mm²) according to
national and local regulations and conditions must be in place.
•
Note that ventilation openings must be kept clear.
−
The air at the ventilation openings must be able to circulate freely.
−
During the entire operating time, no leaves, dirt, etc. must be sucked in from the ventilation
openings.
•
Protect the system against penetrating water (groundwater or flood hazard area).
•
Keep the existing housing doors closed.
Summary of Contents for DVK-GSS0608 001-AA
Page 1: ...StoraXe PowerBooster Kompaktes Speichersystem Compact storage system GSS0608...
Page 4: ......
Page 5: ......
Page 6: ......
Page 23: ...Kurzanleitung DE Version 1 0 GSS0608 Seite 13 von 32 1 7 Sockelzeichnung...
Page 24: ...Kurzanleitung DE Seite 14 von 32 GSS0608 Version 1 0 1 8 Checkliste zur Inbetriebnahme...
Page 25: ...Kurzanleitung DE Version 1 0 GSS0608 Seite 15 von 32...
Page 27: ...Kurzanleitung DE Version 1 0 GSS0608 Seite 17 von 32 1 10 Anhang Auszug aus E Plan...
Page 38: ...Quick guide EN Seite 28 von 32 GSS0608 Version 1 0 2 7 Bottom view of units...
Page 39: ...Quick guide EN Version 1 0 GSS0608 Seite 29 von 32 2 8 Checklist for commissioning...
Page 40: ...Quick guide EN Seite 30 von 32 GSS0608 Version 1 0...
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 55: ......