<4. Wiring>
25
IM 01E25A01-01EN
Unit: mm (approx. in.)
F0403.ai
20(0.79)
TRANSMITTER
ø10.5(0.41)
D
G
90(3.54)
55(2.17)
90(3.54)
F
E
SA
SB
A
C
B
A
C
B
(WHITE)
(WHITE)
(RED)
(BLACK)
(BLACK)
(RED)
L (Specified Length)
SENSOR
8(0.31)Max.
8(0.31)Max.
±5
150 (5.91)
±5
150 (5.91)
Cable Finish: Finished
Specification Code
Length
Description
D
E
F
G
AX01C-C
60 (2.4)
25 (1.0)
70 (2.8)
50 (2.0)
For AXW4A
AXFC-4-L
70 (2.8)
25 (1.0)
50 (2.0)
60 (2.4)
For AXFA11
F404.ai
CAP
ø10.5(0.41)
L (Specified Length) + 340(13.39) (Length for Cable Finish)
Cable Finish: Unfinished
Figure 4.2.3 Cable Finish for Signal Cable
CAUTION
• As crimp terminals A, B, SA, SB and C have their
own electrical potentials, securely insulate them so
as not to come in contact with one another.
• To prevent a shield from coming in contact with
another shield or the case, cover each shield with a
vinyl tube or wrap it in vinyl tape.
4.2.3 Recommended Cable for Modbus
communication
3-Wire cable (twisted pair and Common) with shield
should be used.
Wire gauge: AWG24 or wider
Characteristic Impedance of cable: 100Ω or more
4.3 Electrical Connections
This instrument is of watertight construction as stipulated
in JIS C 0920. It is shipped with a wiring bracket
(waterproof gland, waterproof gland with union or a
plastic gland attached), only in cases where an optional
specification is selected for the electrical connection.
Cable gland has the following kinds depending on the
type and size.
Integral Type Flowmeter
AXW (Size: 500 to 1000 mm (20 to 40 in.))
Optional
Code
Description
EG2
2 pcs. of waterproof gland, and a blanking plug
EG3
3 pcs. of waterproof gland
EU2
2 pcs. of waterproof gland with union joint, and a blanking
plug
EU3
3 pcs. of waterproof gland with union joint
EP2
2 pcs. of plastic gland, and a blanking plug
EP3
3 pcs. of plastic gland
Remote Sensor
AXW (Size: 500 to 1800 mm (20 to 72 in.))
Optional
Code
Description
EW
2 pcs. of waterproof gland with JIS G3/4 female
EG
2 pcs. of waterproof gland
EU
2 pcs. of waterproof gland with union joint
Remote Transmitter
AXW4A
Optional
Code
Description
EG4
4 pcs. of waterproof gland, and a blanking plug
EG5
5 pcs. of waterproof gland
EU4
4 pcs. of waterproof gland with union joint, and a blanking
plug
EU5
5 pcs. of waterproof gland with union joint
EP4
4 pcs. of plastic gland, and a blanking plug
EP5
5 pcs. of plastic gland
Remote Transmitter
AXFA11G
Optional
Code
Description
EW
5 pcs. of waterproof gland with JIS G3/4 female
EG
5 pcs. of waterproof gland
EU
5 pcs. of waterproof gland with union joint
EP
5 pcs. of plastic gland
IMPORTANT
Apply a blanking plug to the unused electrical
connection. Seal the electrical connections properly
comply to usage state.
W
iring