In the example in grey, this results in:
Byte 2 = 0x01, which means the alarm is active
Byte 3 = 0x18 i.e. 24 in decimal, the brightness rate is therefore 24% when the alarm is triggered.
4.1.11
Digital Input alarm frame
This frame (0x51 for Digital Input 1 button or 0x52 Digital Input 2 terminal block) is sent during the detection of a certain number of events
(determined by register S381 for the button and S383 for the terminal block).
0
1
2
3 à 6
7 et 8
Code
Status
PAYLOAD
0x51 or 0x52
Status
Digital Input X states
Digital Input X global counter
Digital Input X instant counter
0x51
0xA3
0x01
0x0000017E
0x0001
Description of the frame:
• Byte 2: state of the digital input when sending the previous frame and state of the current of the digital input:
• Byte 1: state of the digital input when sending the previous frame
• 0: OFF / OPENED
• 1: ON / CLOSED
• Bit 0: current state of the Digital Input
• 0: OFF / OPENED
• 1: ON / CLOSED
• Bytes 3 and 6: Global counter of the Digital Input (automatically loops when the limit linked to the size of the counter is reached)
• Bytes 7 and 8: Instantaneous counter of the Digital Input (no automatic loop back, this will lock at 0xFFFF).
In the example in grey, this results in:
• Byte 0 = 0x51, so this concerns an alarm on the button (TOR1)
• Byte 2 = 0x01, which means that the last time a frame left the button was not enabled (0) but this time it is (1).
• Byte 3 to 6 = 0x0000017E, i.e. 382 in decimal, which means that there have been 382 button presses since the device was started
• Bytes 7 to 8 = 0x0001, i.e. 1 in decimal, there has only been one button press since the last frame was sent
4.1.12
Summary of the conditions for sending the upstream frames
The table below summarizes the conditions for sending the various uplink frames:
Code
Description
Sending conditions
0x10
Information frames on device configuration
Device start up
Exit configuration mode
Receiving a 0x01 downlink
0x1F
Information frame on configuration of Digital Input(s)
Device start up
Exit configuration mode
0x20
Information frames on Network configuration
Device start up
Exit configuration mode
Receiving a 0x02 downlink
0x30
Keep Alive frame
Periodically in pure event mode
0x31
Reply frame to a register value request
Receiving a 0x40 downlink
0x33
Response frame following an update of register(s)
Receiving a 0x41 downlink
0x4E
Periodic reading frame (presence and luminosity)
According to defined period
0x4F
Presence-alarm frame
Exceeding a number of detections
0x50
Brightness threshold alarm frame
Exceeding threshold
0x51
Button alarm frame (Digital Input 1)
By default, at each press of the button
Exceeding a threshold if configured
0x52
Terminal alarm frame (Digital Input 2)
By default, at each press of the button
Exceeding a threshold if configured