7.1.
Led status indication
Number of flashes for error (red)
1x
Problem with GSM module
2x
No SIM card detected
3x
Incorrect pin code
4x
PUK code necessary
5x
Power failure
6x
No SMS central number / no antenna level
7x
No telephone number coupled to input / 2G/4G connection cannot be
established / Ethernet error
8x
Connection to external server cannot be established
Number of flashes for network (orange)
Off
No antenna
Constant
Connected to external server
1x
Antenna level 1% < > 20%
2x
Antenna level 21% < > 40%
3x
Antenna level 41% < > 60%
4x
Antenna level 61% < > 80%
5x
Antenna level 81% < > 100%
Faster
Establishing connection (clientmode)
Number of flashes for on/busy (green)
Off
SVA is switched off
On
SVA is switched on
Faster
Starting up / sending message
1x
Input 1 active
2x
Input 2 active
3x
Input 3 active
4x
Input 4 active
5x
Input 5 active
6x
Input 6 active
7x
Input 7 active
8x
Input 8 active
7.2.
Technical specifications
Systeemeigenschappen
SVA0000-I
Type of detector:
a
larm dialler | (Web
l
ogger|
m
odem)
Number of digital inputs
Number of GPIO inputs
Number of PT100 inputs
Number of relay outputs
I=4G variant
Input/output options (differs for each SVA model)
No.
Digital contact input (NO/NC)
4 - 8
Digital voltage input (5 - 24VDC )
4 - 8
Relay outputs
0 - 2
Hardware
4201 4G
4211 4G
Type I/O
SVA4002-I
SVA2000-I
SVA8000-I
Contact inputs
max. contactresistance
max. Vinl
ow
0 - 8
1kΩ
1V
0 - 8
1kΩ
0.4V
Digital inputs (5 - 24VDC)
Abs. Vmax level
Vnom
max
Vmin
hoog
Vmax
laag
4 - 8
30V
24V
2.0V
1.5V
4 - 8
30V
24V
2.5V
2.0V
Inputs are protected against 24VAC. However, they are not suitable for measuring / detecting AC signals in
Voltage / Contact or Digital Input mode.