INSTALLATION AND SETUP GUIDE
GENERAL INFORMATION
The 5800RL is a relay module that enables use of remote sounders
and/or remote arm/disarm indicators using two relays activated by
wireless signals from the LYNX control (see Figure 1). The 5800RL
can also send tamper and supervision signals to the LYNX if so
programmed. The 5800RL is compatible with LYNX controls
having software versions 9.0 or higher. Refer to the LYNX control
installation and setup guide for software compatibility and zone
programming.
5800RL
RELAY
MODULE
TAMPER AND
SUPERVISION
SIGNALS SENT
TO CONTROL
MODULE'S 2
RELAYS ARE
ACTIVATED BY
SYSTEM
CONDITIONS
AWAY
OFF
STAY
AUX
5800RF-004-V0
Figure 1. Lynx Interface Diagram
MOUNTING LOCATION GUIDELINES
Use the following guidelines when selecting a mounting location for
the 5800RL Relay Module (see figure 2):
•
Mount the 5800RL in a high location for best wireless
reception.
•
Do not mount the 5800RL on or near metal objects. This
decreases range and/or blocks wireless transmissions.
•
Locate the 5800RL at least 10 feet from any remote keypad to
avoid interference from the microprocessors in those units.
•
To avoid voltage loss that occurs on long power lines, mount
the external power supply unit in close proximity to the
5800RL
.
Mounting, Wiring, and Setup
IMPORTANT:
Before permanently mounting the 5800RL,
perform the setup procedure described in the Setting Up the
5800RL section
.
1.
Remove the 5800RL's cover from the base (using a small flat
head screwdriver, insert screwdrivers tip in slot at top of the
cover to remove).
2.
Using the 5800RL base as a template, position in the desired
location and mark the two mounting holes. See Figure 2 for
mounting hole location.
3.
Attach the 5800RL base using the fasteners supplied.
Screws and plastic anchors are suitable for a typical
installation, but you may use any two fasteners that secure the
base firmly to the mounting surface.
4.
Connect relay and power wiring to the 5800RL’s terminals.
Refer to Figure 3 for a typical relay application.
The 5800RL can be powered from either an AC transformer or DC
power supply external power source connected to terminals 7 and 8
(see figure 3).
Power source ratings are as follows:
Type
Rating
AC
9VAC, 15VA (e.g., ADEMCO 1332 transformer)
DC
12VDC, 100 ma (power supply)
NOTE: Use of power sources with higher or lower voltages may
result in damage or failure to operate properly. Non-ADEMCO
power supplies may have connectors installed. Remove these
connectors prior to attempting to connect power supply to 5800RL.
TAMPER
SWITCH
2 - NO
3 - COM
4 - NC
5 - NO
6 - COM
7 - AC OR DC (+) IN
1 - NC
8 - AC OR DC ( ) IN
RELAY A
RELAY B
5800RL-001-V1
LED
(RED)
LED
(YELLOW)
LED
(GREEN)
RF INTERFERENCE
LED (RED)
ANTENNA 2
ANTENNA 1
DIP
SWITCH
MOUNTING
HOLE
MOUNTING
HOLE
1 2 3 4 5 6
ON
OFF
Figure 2. 5800RL Diagram
2 - NO
3 - COM
4 - NC
5 - NO
6 - COM
7 - AC OR DC (+) IN
1 - NC
8 - AC OR DC ( ) IN
RELAY A
RELAY B
5800RL-005-V0
ANTENNA 2
SOUNDER
ANTENNA 1
1 2 3 4 5 6
ON
OFF
ADEMCO AD12612
AUX PWR SUPPLY
(12 VDC)
AC
IN
+
_
DC
OUT
1361
+
_
RED
BLA
CK
POWER SUPPLY
BACKUP
BATTERY 12VDC
+
PWR SUPPLY
XFMR
16.5VAC
Figure 3. Typical Sounder Wiring Installation
Referring to RELAY AND LED Description and Figure 4, Set up
the 5800 RL as follows:
5.
Set DIP switches 2-6 (figure 4) to the appropriate House ID (1-
31). Make sure the House ID set by the DIP switches matches
that entered in the LYNX control.
6.
If module supervision and/or tamper protection is desired,
program the 5800RL’s tamper/supervisor loop (1) as a zone and
enroll its serial number.
Note the following when enrolling:
Zone Type = 5 (trouble by day/alarm by night)
Input Type = 3 (RF)
Loop Number = 1
7.
Position the wiring in the exit slot and reinstall the 5800L’s
cover on the base.
Test the 5800RL module with the rest of the system.