Page 1: ...de see instructions accompanying those units If desired momentary type normally open emergency panic switches e g No 219 may be connected across the remote stations YELLOW AND RED leads instead of swi...
Page 2: ...described above Connect each remote station s leads as shown in Diagram 1 Connections to the No 21612 Adapter to be installed within the control will be made later In each No 5212 Remote Station used...
Page 3: ...cabinet 6 Connect the No 216 12 remaining leads to the control as indicated in Diagram 1 CAUTIONS The BLUE BLACK leads supply power to the No 216 12 Polarity must be observed or a burnout will result...
Page 4: ...ON The No 102312 Alarm Processing Center features automatic loop shunting and may be armed even though one or both of its basic protection zones not the delay zone has a fault and the No 21512 s LED...
Page 5: ...SWITCHES N O MOMENTARY MAY BE I OPTIONALLY CONNECTED IN PARALLEL ACROSS I REQ D YEL AND RED LEADS 0 gy NO 5212 i REMOTE E SlA lON S z OBSERVE iI POLARITY I BLUE II QUICK CONNECT TERMINAL TO TERM 2 RE...
Page 6: ...reviously a At a No 21512 or 5212 Remote Station momentarily press the buttons marked and l simultaneously The panic alarm will sound or a silent alarm will be sent and continue until the PANIC RESETs...