800-357-104-01, Revision 01
Appendix A - System Specifications
HMS-357 List 4 and List 5
September 29, 2000
83
Table 18.
Common Equipment Power Consumption
Equipment
Current Draw (mA)
Power Consumption
(Watts)
Power Dissipation (Watts)
HXU-357 List 1 (2 units)
353 typ. 612 max.
15 typ. 26 max.
15 typ. 26 max.
HMU-319 List 7
118 typ. 141 max.
5 typ. 6 max.
5 typ. 6 max.
HFA-357
250 typ. 306 max.
11 typ. 13 max.
12 typ. 13 max.
Total System Power Consumption
1074 typ. 1671 max.
46 typ. 71 max.
47 typ. 71 max.
Table 19.
Power Consumption and Power Dissipation for Multisystem Configurations
Line Type as
defined in
Four Systems (Watts)
Five Systems (Watts)
Six Systems (Watts)
Consumption
Dissipation
Consumption
Dissipation
Consumption
Dissipation
A
1048 typ.
1236 max.
688 typ.
833 max.
1310 typ.
1545 max.
859.4 typ.
1042 max.
1572 typ.
1855 max.
1031 typ.
1250 max.
B
1101 typ.
1294 max.
768 typ.
922 max.
1376 typ.
1618 max.
960 typ.
1153 max.
1651 typ.
1941 max.
1152 typ.
1383 max.
C
1583 typ.
1824 max.
850 typ.
1012 max.
1978 typ.
2280 max.
1062 typ.
1265 max.
2374 typ.
2736 max.
1275 typ.
1518 max.
D
2131 typ.
2428 max.
983 typ.
1143 max.
2664 typ.
3035 max.
1229 typ.
1429 max.
3197 typ.
3642 max.
1475 typ.
1714 max.
E
2747 typ.
3105 max.
1095 typ.
1264 max.
3434 typ.
3882 max.
1369 typ.
1580 max.
4121 typ.
4658 max.
1643 typ.
1896 max.
F
2837 typ.
3204 max.
1084 typ.
1252 max.
3546 typ.
4005 max.
1355 typ.
1565 max.
4255 typ.
4806 max.
1626 typ.
1878 max.
These configurations require fans to meet NEBS.
These configurations do not meet NEBS. The rack is limited
(230 W of heat dissipation per chassis, 948W per rack)
to 1275 W of heat dissipation. The floor lineup must be
changed to accommodate this configuration.