the FLA at 1000VDC for 1 minute. At the end of 1 minute, the insulation resistance should be greater than 2G ohms. If the
resistance is less than 2G ohms, replace the FLA.
Figure 2: FLA Field Insulation Resistance Check
Megger
Jumper
Airfield Lighting Field Lightning Arrestor
Troubleshooting
12