66
A.07.370e - Edition 2.0
Technical data
7.2 Applicable standards
The equipment is in accordance with these standards:
Table: 7.3
Applicable standards
7.3 ElectroMagnetic Compatibility (EMC)
The equipment is designed to operate in an industrial electro-magnetic environment. The regulator complies
with IEC 61822, in accordance with IEC 61000-6-4 and IEC 6-6-2 (generic standard for industrial
environment). The equipment is, with adapted test levels, in accordance with IEC/TS61000-6-5, G
(substation environment, location G).
CRE 10 10.0
1.50
10
2.2 kV
RMS
, 4.2 kJ
CRE 15 15
2.30
12
3.0 kV
RMS
, 5.6 kJ
CRE 20 20
3.03
15
4.5 kV
RMS
, 8.4 kJ
CRE 25 25
3.80
19
5.2 kV
RMS
, 9.8 kJ
CRE 30 30
4.54
23
6.0 kV
RMS
, 11.2 kJ
1)
Test condition: 50 Hz sinosoidal wave for 1 minute. The test is done without output overvoltage protections.
Type
Rated output
power [kW]
RMS output voltage
at 6.6 A RMS output
current [kV]
Insulated test on
output
1
[kV]
Output overvoltage
protection 25kApk
Standard
Description
ICAO
Aerodrome Design Manual, Part 5 paragraphs 3.2. (current
edition)
FAA
AC 150/5345-10 (current edition), L-828 and L829 except for
input voltage
IEC
IEC 61822
CENELEC
EN 61822
CE certfied
Summary of Contents for CRE 10
Page 1: ...A 07 370e Edition 2 0 Installation Manual Constant Current Regulator Type CRE ...
Page 14: ...14 A 07 370e Edition 2 0 Safety ...
Page 44: ...44 A 07 370e Edition 2 0 Inspection and transport ...
Page 64: ...64 A 07 370e Edition 2 0 Installation ...
Page 85: ...A 07 370e Edition 2 0 85 Technical data ...
Page 86: ...adbsafegate com ...