6.9 Connect power input supply, stackable cabinet
Disassemble the connector
1. Remove the screws (A).
2. Remove the terminal block (B).
Connect - 1
1. Put the cable gland over the input cable (A).
2. Put the input cable through the connector (B).
3. Strip the wires (C) approximately 100 mm.
4. Connect the wires to the pins in the terminal block (E).
5. Connect the earthing wire (D) to the pin 2.
6. Connect the earthing wire to the earthing network (A) of the
substation.
Connect - 2
1. Install the terminal blocks to the connector.
2. Examine if the numbers on the connector correspond with the numbers on the input connector on the
equipment.
3. Install the connector to the equipment.
4. Close the clamps of the connector.
A
A
B
Input [V]
Pin 1
Pin 3
208-230
Phase
Neutral
380-400
Phase
Phase
A
B
C
D
E