WaterMaster® 120 Evo
8
6
2
5
11
1
3
4
42
A1009341-664Y8300 • B
REMOVAL AND INSTALLATION OF THE
BURNER - WM 120 EVO
Set-up conditions
•
Appliance shut down
•
External power supply isolated
•
Gas supply closed
•
Front and top panels removed (refer to ML booklet).
•
lation of the Burner Electrode" on page 40
) .
Removal procedure
1. Disconnect all plugs from the fan assembly (
11
) and
the gas valve (
2
) and any grounding cable, as re-
quired.
2. Release clamp and remove air inlet hose from el-
bow (
3
).
3. Disconnect the air inlet elbows (
3)
from the venturi
(
5
).
4. Disconnect the gas connection (
1
) flange from the
gas valve (
2
) by releasing four screws. Retain hard-
ware for reinstallation.
5. Discard O-ring.
6. Using a socket wrench, release the burner hood (
8
)
attaching hex. screws and retain them for reinstal-
lation.
7. Lift the burner assembly and pull it out of the ex-
changer with its insulation.
8. If required, clean the exchanger, see
.
Installation procedure
1. Reinstall the burner assembly with its insulation
into the exchanger.
2. Install the retaining screws of the burner hood
(
8
) and fasten them in a crosswise pattern at the
required tightening torque (refer to
3. Install a new O-ring on the gas connection (
1
)
flange.
4. Reconnect the gas connection (
1
) flange to the
gas valve (
2
)
using four retained screws.
When connecting the air inlet, make sure that
the check valve (4) is correctly located at the
elbow (3) end.
5. Reconnect the air inlet elbows (
3
).
6. Install the air inlet hose on the elbow (
3
) and se-
cure with retained clamp.
7. Reconnect the plugs to the gas valve (
2
) and the
fan assembly (
11
), and any disconnected ground-
ing cable.
Follow-on tasks
1. Install the electrode. Refer to
and Installation of the Burner Electrode" on page
EN
Maintenance
Summary of Contents for WaterMaster 120 Evo
Page 48: ...ACV International Oude Vijverweg 6 B 1653 Dworp Belgium belgium service acv com www acv com...
Page 49: ...A1009341_664Y8300 B WaterMaster 25 35 45 70 85 120 Evo 25 45 70 X Evo ML...
Page 57: ...9 x4 x4 x4 1 2 x2 ML...
Page 59: ...11 x7 WM 25 35 45 Evo x9 WM25X 45X 70 85 120Evo x11 WM 70 X Evo x3 x2 ML...
Page 60: ...12 WaterMaster 70 X Evo x4 ML...
Page 61: ...13 6 3 2 1 x4 x4 WaterMaster 25 X 35 45 X 70 85 120 Evo ML...
Page 75: ...31 ML...
Page 76: ...ACV International Oude Vijverweg 6 B 1653 Dworp Belgium belgium service acv com www acv com...