27
Installer's Handbook (Evo) - 660Y3000 • A
EN
APPLIANCE CODES
Appliance type
Model
Natural gas
Propane
HeatMaster C Evo
25
A411
A412
HeatMaster TC Evo
25
A421
A422
35
A431
A432
45
A441
A442
70
A451
A452
85
A461
A462
120
A471
A472
WaterMaster Evo
25
A621
A622
25X
A821
A822
35
A631
A632
45
A641
A642
45X
A841
A842
70
A651
A652
70X
A851
A852
85
A661
A662
120
A671
A672
CH Parameters
Factory Settings
EZ Setup
reset
Installer
reset
HeatMaster
WaterMaster
Heating Operation
Enabled
Disabled
Enabled
Demand
Thermostat &
setpoint
—
Thermostat &
setpoint
Thermostat &
setpoint
CH Maximum Capacity
100%
—
CH Minimum Capacity
0%
—
Absolute Max CH Setpoint
87°C
—
85°C
CH1 Max Setpoint
82°C
—
82°C
82°C
CH1 Min Setpoint
27°C
—
27°C
27°C
Outdoor Curve Coldest Day
-12°C
—
-12°C
Outdoor Curve Warmest Day
18°C
—
18°C
CH2 Circuit
Enabled
—
Enabled
CH2 Max Setpoint
60°C
—
60°C
60°C
CH2 Min Setpoint
27°C
—
27°C
27°C
Warm Weather Shutdown
Off
—
Off
Off
Circulation pump permanent
Disabled
—
Disabled
CH Post Pump time
5 min
—
5 min
Freeze Protection
Enabled
—
Enabled
Frost Protection Setpoint
-30°C
—
-30°C
Parallel Shift Value
0°C
—
0°C
CH Call Blocking
2 min
—
2 min
Appliance min CH setpoint
27°C
—
DHW Parameters
DHW Operation
Enabled
Enabled
Enabled
Demand
Sensor
Sensor
Sensor
Sensor
DHW Boost
Disabled
Disabled
DHW Boiler Setpoint
75°C
75°C
75°C
DHW Setpoint
60°C
60°C
60°C
60°C
DHW on Differential
3°C
3°C
3°C
DHW Storage Adder
15°C
15°C
15°C
DHW Post Pump Time
2 min
2 min
2 min
DHW priority Timeout
Off
Off
Off
Off
DHW priority
Enabled
Enabled
Enabled
DHW Call Blocking
0 min
0 min
0 min
DHW to CH Call Blocking
1 min
1 min
1 min
Antilegionella Function
Enabled
Enabled
Enabled
FACTORY SETTINGS AND RESET VALUES
DESCRIPTION AND OPERATION