Run Output is configurable to indicate that the unit is running. There are two configurations in which this can be set:
• Either the compressor or the Indoor Fan only is running
• Only Compressor is running.
By default, this is set to turn on when either indoor fan or compressor is operating. To set up to compressor run
indication only, in OD Board Menu follow below steps.
1. Using the
MENU
and the
ENTER
Buttons on the outdoor PCB, navigate to
SEt
(Settings)
→
run
(Unit Operation
Indicator Settings).
2. If required, press
MENU
to navigate to
YES
.
Remote On/Off
CONDENSER
CPU BOARD
OPTIONAL
REMOTE
ON OFF SWITCH
Turning the system On and Off by remote method
Turning the
system On
St atus 1: The system is Off and the remote switch/relay has
been left in the open position.
1. Close remote switch/relay.
2. System will start in approximately 1 minute.
St atus 2: The system is Off and the remote switch/relay has
been left in the closed position.
1. Open remote switch/relay for a minimum of 5 seconds.
2. Close remote switch/relay.
3. System will start in approximately 30 seconds.
Turning the
system Off
St atus 3: The system is On and the remote switch/relay has
been left in the closed position.
1. Open remote switch/relay.
2. System will turn Off in approximately 1 minute.
St atus 4: The system is On and the remote switch/relay has
been left in the open position.
1. Close remote switch/relay for a minimum of 5 seconds.
2. Open remote switch/relay.
3. System will turn Off in approximately 30 seconds.
COM
12V