Example 6: Set the buffeting elimination time of the remote communication unit with instrument address 1.
Send: 0x01,0x10,0x51,0x00,0x00,0x01,0x02,0x00,0x04,0Xe7,0x56
Return: 0x01,0x10,0x51,0x00,0x00,0x01,0x11,0x35
Note: The buffeting elimination time is set to 4ms (buffeting elimination time: in the vibration environment, the
stroke switch or button often sends out the wrong signal due to buffeting, and the buffeting time is generally short.
According to the characteristics of short buffeting time, the reliable and effective signal after buffeting elimination
can be obtained by setting the buffeting time of the ARTU remote communication unit, so as to achieve the purpose
of the anti-interference).
6. Appendixes
6.1 Dial switch settings
6.1.1 Dial code definition
1
2
3
4
5
6
7
8
9
10
Address settings
1
0
0
0
0
Baud-rate
settings
0
0
Mode
settings
0
Communication mode settings
0
0
6.1.2 Address settings
Dial code 1
Dial code 2
Dial code 3
Dial code 4
Dial code 5
Address
1
0
0
0
0
1
0
1
0
0
0
2
- - - - - - -- - - - -- - - - - -- - - - - -- -
1
1
1
1
1
31
0
0
0
0
0
32
6.1.3 Baud-rate settings
Baud-rate
Dial code 6
Dial code 7
9600bps
0
0
4800bps
1
0
38400bps
0
1
19200bps
1
1
6.1.4 Mode settings
Dial code
8
Note: Reset dial code 8 and the address
or baud rate at the same time so as to
work in a new communication mode.
Instrument local address and baud-rate
settings
0
Upper computer address and baud-rate
settings
1
6.1.5 Format settings
Mode
Dial code
9
Dial
code 10
10 bits: 1 start bit, 8 data bits and 1 stop bit.
0
0
11 bits: 1 start bit, 8 data bits and 2 stop bits (reserved).
1
0
11 bits: 1 start bit, 8 data bits, even parity and 1 stop bit.
0
1
11 bits: 1 start bit, 8 data bits, odd parity and 1 stop bit.
1
1