11
CABLE SIZE
Cooling only
Model
Unit
A5DB80H
A5DB100H
A5DB125H
A5MC80H
A5MC100H
A5MC125H
Voltage range**
Indoor
380 - 415V / 3Ph /50Hz + N +
Outdoor
380 - 415V / 3Ph /50Hz + N +
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
mm
2
mm
2
mm
2
1.0
2.5
2.5
-
5
1.0
2.5
2.5
-
5
1.0
2.5
2.5
5
5
Interconnection cable size*
Number of conductors
mm
2
1
4
1
4
-
-
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
A
A
A
6
32
32
16
32
40
4
40
40
Model
Unit
A5DB150H
A5DB200H2
A5DB250H2
A5MC150H
A5MC100H x 2
A5MC125H x 2
Voltage range**
Indoor
380 - 415V / 3Ph /50Hz + N +
Outdoor
380 - 415V / 3Ph /50Hz + N +
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
mm
2
mm
2
mm
2
1.0
4.0
4.0
5
5
1.0
2.5
6.0
5
5
1.0
2.5
10.0
5
5
Interconnection cable size*
Number of conductors
mm
2
-
-
-
-
-
-
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
A
A
A
6
50
50
10
32
50
16
40
63