COOLING CAPACITY (STANDARD AIR FLOW)
ART100A
OUTDOOR DB
°
C
INDOOR
INDOOR
20.0
25.0
30.0
35.0
40.0
46.0
52.0
DB
°
C
WB
°
C
Q kW
SHC kW
Q kW
SHC kW
Q kW
SHC kW
Q kW
SHC kW
Q kW
SHC kW
Q kW
SHC kW
Q kW
SHC kW
15
27.3
19.6
26.9
19.6
26.2
19.4
25.6
19.2
24.9
18.9
24.0
19.0
23.1
18.7
20
16
28.1
18.0
27.6
17.6
27.0
17.5
26.0
17.2
25.1
16.8
24.8
17.1
24.1
17.1
16
28.1
24.7
27.6
24.8
27.0
24.8
26.0
24.5
25.1
24.1
24.8
24.8
24.1
24.1
17
28.9
23.1
28.4
23.3
27.8
23.1
27.0
23.0
26.2
22.8
25.7
23.2
25.2
23.0
18
29.8
21.5
29.3
21.4
28.6
21.2
28.0
21.0
27.4
21.1
26.6
21.0
26.3
21.3
19
30.7
19.6
30.2
19.3
29.6
19.2
28.9
19.1
28.4
19.3
27.8
19.4
27.3
19.7
24
20
31.6
17.4
31.1
17.1
30.5
17.1
29.9
17.0
29.4
17.1
28.9
17.3
28.3
17.5
18
29.8
25.9
29.3
26.1
28.6
26.0
28.0
26.0
27.4
26.3
26.6
26.4
26.3
26.3
19
30.7
25.2
30.2
25.1
29.6
25.1
28.9
25.1
28.4
25.6
27.8
25.8
27.3
25.9
20
31.6
24.0
31.1
23.9
30.5
24.1
29.9
24.2
29.4
24.4
28.9
24.9
28.3
25.2
21
32.6
22.5
32.1
22.5
31.4
22.3
30.8
22.5
30.3
22.7
29.8
22.9
29.3
23.4
22
33.6
20.5
33.1
20.5
32.4
20.4
31.8
20.7
31.2
20.6
30.7
20.9
30.3
21.2
23
34.7
19.1
34.2
18.8
33.4
18.7
32.8
19.0
32.2
19.0
31.7
19.0
31.3
19.4
28
24
35.8
17.2
35.3
16.9
34.5
16.9
33.9
16.9
33.3
17.0
32.7
17.0
32.3
17.1
20
31.6
27.5
31.1
27.7
30.5
27.8
29.9
27.8
29.4
28.2
28.9
28.6
28.3
28.3
21
32.6
25.7
32.1
26.0
31.4
26.1
30.8
26.2
30.3
26.4
29.8
26.8
29.3
27.2
22
33.6
23.8
33.1
23.8
32.4
24.0
31.8
24.2
31.2
24.3
30.7
24.6
30.3
24.8
23
34.7
22.2
34.2
22.2
33.4
22.4
32.8
22.3
32.2
22.6
31.7
22.8
31.3
23.1
30
24
35.8
20.4
35.3
20.4
34.5
20.3
33.9
20.3
33.3
20.3
32.7
20.9
32.3
21.3
Note1. * Q : COOLING CAPACITY
SHC : SENSIBLE HEAT CAPACITY
FACTOR FOR VARIOUS AIR FLOW
CMM
90
100
110
120
ART100A
AIR VOLUME
L/S
1500
1670
1830
2000
CAPACITY
0.987
1.000
1.012
1.022
COOLING
COMPRESSOR INPUT
0.996
1.000
1.003
1.007
45