Installation
The correct function of the device within the specific technical data can only be guaranteed, if the
permitted process and environmental conditions (see chapter „Technical data“) will not be exceeded.
Process and environmental temperature
At high process temperatures a heat transfer to the terminal housing can be reduced by isolation of
the medium carrying part of the plant.
Installation notes
Drive the system pressure free prior installation resp. deinstallation of the sensor.
Be also sure that no medium is flowing in the system. At extreme system or medium temperatures
there could exist serious dangers.
The screw-in of the thread process connection by using the terminal housing, the connection plug
resp. the connection cable is not permitted.
The tightening of the thread process connection may only be done at the hexagon by a suitable
spanner and with the maximum permitted torque strength.
The maximum permitted torque strength is 50 Nm.
The housing can be rotated every time, also at operation, mechanically by 330°.
Installation place
The choice of the place of installation of the sensor and the length of the sensor tube are of
considerable importance for the quality and the reliability of the measuring results.
The sensor tip should be completely surrounded by medium.
Position the sensor tip in the area of maximum fluid velocity (pipe center).
The minimum sensor immersion length is L ≥16 mm.