Switch output

Version type GA - PNP switch output

An inductive loads at the pnp switch output, e.g. relays or contactors may only be used with a free-

wheeling diode or a RC protection circuit to avoid high voltage peaks.

The load at the PNP switch output will be connected to the teL of the supply voltage by a 

semiconductor switch contactless and by this bounce-free.

At an activated switching state a positive signal near supply voltage is feed to the output.

At deactivated switching state and at failure of supply voltage the semiconductor switch is shut off.

The PNP switch output is current limited to 0,5 A and is overload and short circuit protected.

The device is suitable for non-coincidence use. Using both outputs the NO and NC outputs leads 

contrary states at trouble-free operation.

In the case of failure or at wire break both electronic switches are opened.

By using a two-channel evaluation, besides the flow monitoring also a function dependent monitoring 

of the sensor can be realized.

Version type WB - relay output

Inductive loads at the relay contacts, e.g. auxiliary contactors or magnetic vents may only be used 

with a free-wheeling diode or a RC protection circuit to avoid high voltage peaks.

The load at the relay output will be connected to the terminal L/+L of the supply voltage.

At an activated switching state the supply voltage of the connection terminal L/+L is feed to the 

output.

At deactivated switching state the output is voltage and potential-free.

The device is suitable for non-coincidence use. Using both outputs the NO and NC outputs leads 

contrary states at trouble-free operation.

In the case of failure or at wire break the terminal NO is potential-free and the terminal NC is 

connected to the terminal L/+L.

By using a two-channel evaluation, besides the flow monitoring also a function dependent monitoring 

of the sensor can be realized.

Summary of Contents for Fluxicont FP

Page 1: ...1 bar to 100 bar Integrated evaluation electronic Direct voltage with PNP switch output Universal voltage with relay output LED bar graph for flow indication Enclosure rotatable for optimal operabilit...

Page 2: ...us The actual technical manual includes instructions for installation electrical connection and inauguration as well as the technical data of the device Modifications that answer the purpose of the te...

Page 3: ...ndex Application 4 Function 4 Safety notes 5 Installation 6 Process and environmental temperature 6 Installation notes 6 Installation place 6 Electrical connection 9 Potential equalization earthing 9...

Page 4: ...l The device measures the flow of a liquid medium with the calorimetric measurement method The calorimetric measuring principle is based on cooling a heated temperature sensor Heat is removed from the...

Page 5: ...ce must be chosen resp checked for compatibility with the respective application requirements contacting materials process temperature An unsuitable material can lead to damage abnormal behavior or de...

Page 6: ...treme system or medium temperatures there could exist serious dangers The screw in of the thread process connection by using the terminal housing the connection plug resp the connection cable is not p...

Page 7: ...l pipes Installation in the ascending pipeline for vertical pipes In hygienic applications installation with minimum 3 inclination because of self draining Conditionally recommended orientation Instal...

Page 8: ...pipes open towards the end The sensor tip should never touch the pipe wall Disturbance influence in the pipe system The sensor requires a fully developed flow profile for correct monitoring For this r...

Page 9: ...ion cable For the connection only suitable cables may be used that fulfills the requirements e g regarding temperature chemical resistance or laying at the place of installation Use only shielded sign...

Page 10: ...le free operation In the case of failure or at wire break both electronic switches are opened By using a two channel evaluation besides the flow monitoring also a function dependent monitoring of the...

Page 11: ...scheme Version type GA Conductor color standard connection cable M12 BN brown WH white BU blue BK black The connection cable in not enclosed in the delivery contents Version type WB Conductor color st...

Page 12: ...anufacturer If the device must be sent back for repair the following informations must be enclosed An exact description of the application The chemical and physical characteristics of the product A sh...

Page 13: ...Y others Material process connection probe process wetted V Steel 1 4404 316L resp 1 4571 316Ti Sensor length L1 mm 0 Process connection type 0 2 G 30 mm Process connection type 3 G 28 mm Process con...

Page 14: ......

Reviews: