Acromag TT231-0600 User Manual Download Page 23

Model TT231-0600

 

 

Two-Wire RTD Transmitter w/USB 

 

 

 

 

 

Acromag, Inc. Tel: 248-295-0880 
 
 

          - 23 -                                   http://www.acromag.com  

- 23 - 

http://www.acromag.com 

 

Over-Scale & Under-Scale Thresholds 

 

TIP – Namur Limits:

  For Namur 

compliant output limits, you 
generally need to produce a linear 
output range from 3.8mA to 
20.5mA, and have a failure high 
limit greater than or equal to 
22.5mA, and a failure low limit less 
than or equal to 3.6mA. 

 

TIP – Error Detection:

  Note that a 

checksum error can be 
distinguished at the output signal 
from a lead break error by 
selecting an under-scale limit that 
is greater than the minimum 
threshold setting.  This is because 
a checksum error always sends the 
output signal to a level that is 
0.4mA below the lowest threshold 
setting until reset (~1.8mA).  If you 
select an under-scale threshold 
value greater than the minimum, 
then you ensure that the 
downscale alarm level limit (0.4mA 
below the threshold) does not 
overlap with the checksum error 
level indication.

 

 

 
Select The Over/Under-Scale Thresholds & Alarm Levels… 

 
This unit allows you to select over-scale and under-scale output range thresholds 
which determine the linear operating range of your output.  They also indirectly 
define the upscale & downscale alarm/error limits, as the downscale detent will be 
set to a current level ~0.4mA below the under-scale threshold, and the upscale 
detent will be set approximately 1.0mA above the over-scale threshold.  In this way, 
a lead break or open sensor fault can be easily discerned from simply an over-range 
or under-range input signal. 
 
The range of adjustment for the under & over-scale thresholds is calibrated at the 
factory and indicated via the “Min” and “Max” value fields adjacent to the slide 
controls.  Note that the threshold levels can vary as much as 10% of span between 
units for the same digital setting, and this will be reflected by differing values for 
Min and Max between units.  The Min/Max limits of adjustment are calibrated at 
the factory. 
 

CAUTION:

  For a low resistance or shorted load, and a high loop supply voltage, 

excessive over-range current does drive excessive power dissipation in the output 
pass transistor of the transmitter and will cause the unit to get warm.  This could be 
troublesome at elevated ambient temperatures and in hazardous environments, 
particularly for output currents near 30mA.   
 

 

Use the 

Under-Range Limit

 slide control to select an approximate under-scale 

threshold.  You have 8 levels of under-scale threshold adjustment between Min 
& Max, typically between 2.1mA and 3.6mA.  Your selection will be indicated in 
the field just above the control. 

 

Use the 

Over-Range Limit

 slide control to select an approximate over-scale 

threshold.  You have 16 levels of over-scale threshold adjustment between Min 
& Max, typically between 21mA and 30mA.  Your selection will be indicated in 
the field just above the control. 

 
After making your adjustments, click the 

“Submit O/U Configuration”

 button to 

write your adjustments to non-volatile EEPROM memory. 
 
The linear operating range of your output is now defined between the limits you 
specified.  Your under-scale and over-scale thresholds indirectly correspond to a 
linear operating reqion that usually extends outside of the input zero and full-scale 
limits you specified.  Additionally, the sensor fault/break detent output levels are 
set outside the linear operating region so that you can discern them from simply an 
over-range or under-range input signal. 
 
You should check your under-scale and over-scale threshold levels.  For example, 
you could disconnect an RTD lead to check your O/U alarm limits, which should be 
~0.4mA below the under-scale threshold for a downscale break, or 1mA above your 
over-scale threshold for an upscale break. 
 

Summary of Contents for TT231-0600

Page 1: ...put Two Wire Transmitter USER S MANUAL ACROMAG INCORPORATED Tel 248 295 0880 30765 South Wixom Road Fax 248 624 9234 Wixom MI 48393 7037 U S A email sales acromag com Copyright 2012 Acromag Inc Printe...

Page 2: ...NS 6 Sensor Input Connections 7 Output Power Connections 8 Earth Ground Connections 10 USB Connections 11 CONFIGURATION SOFTWARE 12 Quick Overview 12 TECHNICAL REFERENCE OPERATION STEP BY STEP 14 Conn...

Page 3: ...e effects of power wiring component sensor or software failure in the design of any type of control or monitoring system This is very important where property loss or human life is involved It is impo...

Page 4: ...wiring Connects to two three or four wire sensors Lead wire compensation 3 wire Up or down scale lead break burnout detection Adjustable output error alarm levels outside of operating range Convenient...

Page 5: ...o lift it from the rail while prying the spring clip back with a screwdriver To attach the module to T type DIN rail angle the top of the unit towards the rail and place the top groove of the module o...

Page 6: ...eir sockets by prying outward from the top with a screwdriver blade Strip back wire insulation 0 25 inch on each lead and insert the wire ends into the cage clamp connector of the terminal block Use a...

Page 7: ...u must connect a short copper jumper wire between input terminals 3 and 4 at the transmitter see below Alternately if you want to compensate for sensor lead wire resistance do not include this jumper...

Page 8: ...nt loop The transmitter output floats off this ground by the voltage drop in the load resistance and lead wire This is very important when making USB Connections and will drive the need for USB isolat...

Page 9: ...reduce this ripple further For large 60Hz supply ripple connect an external 1uF or larger capacitor directly across the load to reduce excessive ripple For sensitive applications with high speed acqui...

Page 10: ...urrent loop The Type II transmitter output terminals have a floating connection relative to earth ground Earth ground is normally applied at the output loop power minus terminal and in common with the...

Page 11: ...so held in common with the USB ground and shield ground The potential of the transmitter s current output pin output minus relative to earth ground will vary according to the load current and load res...

Page 12: ...this manual Device Connect First Connect to Unit Here Scan for connected transmitters and open communications with them Display the model serial number Product Name Manufacturer and Serial Number of...

Page 13: ...that the output should go if a sensor lead breaks Then click the Submit Break Detection button to write your selection to transmitter memory Then a lead break or sensor burnout fault will send the out...

Page 14: ...uld connect a current meter in series in this loop to read the loop current directly not recommended Alternatively you could simply connect a voltmeter across a series connected precision load resisto...

Page 15: ...to connect to the selected device If your transmitter was already connected via USB when you booted this software your screen will look more like the screen at right where the software has already ini...

Page 16: ...mber fields At this point the connected transmitter is ready for configuration and the appropriate configuration fields become active and await your input If you want to see how the connected unit is...

Page 17: ...d be wired to input terminal 4 and the other end of this lead connects to the minus terminal at the sensor In both cases this third wire connection serves as the return path for the excitation current...

Page 18: ...zero temperature For example the Resistance Input Type will use the 0 C pedestal resistor which is 98 8 An equivalent sensor input resistance actually drives the differential signal measurement to 0V...

Page 19: ...il you complete the calibration sequence that is initiated by clicking the Start Calibration button You can use the Get Config Calibration control button to read the current configuration of the unit...

Page 20: ...type the measured current in milliamps into the Measured Current Output field Then click the Go To Step 2 button 2 After clicking Go To Step 2 the following message will be displayed Now the unit need...

Page 21: ...note that it will be closer to the full scale output than it was in step 2 as linearization is ON Type the measured output current in milliamps into the Measured Current Output field Then click the C...

Page 22: ...calibration prompt messages Refer to the following table when using a resistance substitution box to drive the input zero and full scale signals This contains the resistance values for the two most c...

Page 23: ...0 of span between units for the same digital setting and this will be reflected by differing values for Min and Max between units The Min Max limits of adjustment are calibrated at the factory CAUTION...

Page 24: ...ion No Faults 1 IN Exceeds Positive Limit 2 IN Exceeds Negative Limit 3 IN Exceeds Positive Limit 4 IN Exceeds Negative Limit 5 IN Exceeds Positive Limit IN Exceeds Positive Limit 6 IN Exceeds Positiv...

Page 25: ...orrupted A checksum error will also send the output current to 0 4mA below the lowest under scale threshold setting until reset via this control or by toggling loop power OFF ON A persistent checksum...

Page 26: ...ro or increase your full scale value Step 1 Zero calibration Please set your input resistance to X Ohms Measure the corresponding output current and enter the measured value into the Measured Current...

Page 27: ...rmal operation Setup involves selecting the input type Pt RTD or Resistance input wiring 2 wire 3 wire 4 wire the Pt RTD alpha coefficient the input range zero 50 C 0 C or 0 F the input range full sca...

Page 28: ...s without making a separate measurement Refer to the block diagram to gain a better understanding of how this transmitter works A third sensor wire is used to compensate the sensor for the resistance...

Page 29: ...nonlinear response over temperature that is approximated by a quadratic equation The linearity DAC uses positive feedback from the input signal to produce a system response that is also nearly quadrat...

Page 30: ...cable to the transmitter Communication or power was interrupted while USB was connected and the configuration software was running Close the current connection with the software re scan the transmitte...

Page 31: ...ue URV This is the Down scale alarm level and indicates the input signal exceeds the common mode range of the input This can also occur if the third sensor wire is missing 3 4 wire RTD a lead has brok...

Page 32: ...ction or a small jumper wire between terminals 3 4 at the transmitter 2 wire connection You may have damaged the input PGA via a ground loop or incorrect wiring If you cannot get the output signal to...

Page 33: ...cale verification The enclosure is not meant to be opened for access and can be damaged easily if snapped apart Thus it is highly recommended that a non functioning transmitter be returned to Acromag...

Page 34: ...ansmitter USB Isolator USB Isolator Order USB ISOLATOR USB Signal Isolator USB A B Cable 4001 112 Instructions 8500 900 This kit contains a USB isolator and a 1M USB A B cable for connection to a PC T...

Page 35: ...RTD 0 00385 C 3 wire 0 C to 200 C input 4 to 20mA output and upscale fault detection Recalibration of any model will require use of an TTC SIP configuration kit ordered separately see Accessories Mod...

Page 36: ...put Filter Bandwidth 3dB at 700Hz typical normal mode filter Input Linearization Preset for input Additive to excitation current to accomplish linearization of Pt RTD inputs Correction is digitally ad...

Page 37: ...oltage 30mA max The voltage level across the transmitter must not exceed 36V even with a shorted load The voltage level must be chosen to provide 20mA current to the load 0 020 R typical plus 8 6V min...

Page 38: ...l Upscale fault level is 1 0mA above the selected over scale threshold typical The unit can be set for limits that comply with NAMUR NE43 recommendations USB Interface Includes a USB socket for tempor...

Page 39: ...solid copper wire Program Connector USB Mini B type 5 pin See USB Interface Case Material Self extinguishing polyamide UL94 V 0 rated color light gray General purpose NEMA Type 1 enclosure Circuit Bo...

Page 40: ...n Controlled GBGC Temperature TT231 0600 25 C 3 140 003 hrs 40 C 2 353 528 hrs Configuration Controls Software Configuration Only via USB This transmitter produces an analog output current proportiona...

Page 41: ...Revision 01 JUNE 12 A BC KLK Initial Acromag release 26 JULY 13 B CAP ARP Added UL Mark to this model removed pending refer to ECN 13G017 for additional information Added note to USB connections draw...

Reviews: