MiniPuck Model ST132-06x0 Two-Wire TC/mV Transmitter
________________________________________________________________________________
______________________________________________________________________________________
Acromag, Inc. Tel:248-295-0880 Fax:248-624-9234 Email:
3
The ST132-0600 is an ANSI/ISA Type II transmitter designed to interface
with a TC (Thermocouple) sensor, or ±100mV input, and modulate a 4-
20mA current signal for a two-wire current loop. This unit is setup and
calibrated using the included software and a USB connection to Windows-
based PC’s. The unit provides automatic cold junction compensation,
linearization, and lead break or sensor burnout detection. It also offers a
scalable input range.
•
Digitally setup and calibrated via USB
•
Flexible TC or millivolt input support
•
Provides selectable upscale or downscale Lead-Break Detection
•
Adjustable Linearization.
•
High Measurement Accuracy
•
Non-Polarized Output/Power Connection
•
Programmable/Scalable Input Range Scaling
•
Convenient Two-Wire Loop Power
•
Designed For DIN Form B Sensor Head Mounting
•
Provides a Linearized Output Response
•
Easy USB Reconfiguration and Calibration with Included Software
•
Wide Ambient Operation
•
Hardened For Harsh Environments
•
Optional DIN Rail Adapter
•
CE Approved
•
Model ST132-0610 is UL Listed (USA & Canada) suitable for use in
Class I, Division 2, Groups A, B, C, D Hazardous Locations, or
Nonhazardous Locations only.
•
Model ST132-0610 is ATEX Certified for Explosive Atmospheres.
II 3 G Ex nA IIC T4 Gc -40
o
C
≤ Ta ≤ +80
o
C
DEMKO 13 ATEX 1113348X
This transmitter is designed for mounting in DIN Form B connection/sensor
heads commonly used in thermowell applications for sensing temperature or
for use in an enclosure with suitable strength and rigidity. Optionally, a DIN-
rail adapter may be purchased for mounting the unit to T-type, or G-type
DIN rail. The transmitter must be installed in an ATEX Certified enclosure
with a minimum ingress protection rating of at least IP54. Enclosure must
have a door or cover accessible only by the use of a tool (See page 28 for
details).
Its non-isolated input is intended to mate with non-grounded, type J, K, T, R,
S, E, B, & N thermocouple temperature probes common to these thermowell
applications. It provides an output current linearized to the TC sensor
temperature. Optionally, it can support simple millivolt inputs and drive an
output current linear to the voltage.
The output signal is transmitted via a two-wire, 4-20mA current loop. The
two-wire current signal can be transmitted over long distances with high
noise immunity. Sensor lead-break detection and the inherent live-zero
output offset offers convenient I/O fault detection, should an I/O wire break.
DESCRIPTION
Key Features
Application