MiniPuck Model ST132-06x0 Two-Wire TC/mV Transmitter
_________________________________________________________________________________
______________________________________________________________________________________
Acromag, Inc. Tel: 248-295-0880 Email:
28
Enclosure & Physical
General purpose plastic enclosure intended to be mounted in DIN Form
B connection heads. Optionally, a DIN rail adapter is available for
mountable
to 35mm “T-type” DIN rail, or G-Type DIN rail.
Dimensions
: Diameter = 44.5mm (1.752 inches), Height = 23.4mm
(0.921 inches). Refer to Mechanical Dimensions drawing. Conforms to
DIN 43 729 Form B size requirements.
I/O Connectors:
Barrier strip type, captive screw terminals; wire range:
AWG #14-28 solid or stranded.
Program Connector:
USB Mini B-type socket, 5-pin.
Case Material:
Self-extinguishing polycarbonate ABS plastic, UL94 V-0
rated base material, color blue. USB dust cap material is Santoprene,
251-70W232, color red.
Terminal Material:
Captive 4-40 threaded steel screw and 0.040 inch
thick Phosphor-Bronze terminal material.
Circuit Board:
Military grade fire-retardant epoxy glass per IPC-
4101/98 with humi-seal conformal coating.
DIN-Rail Mounting:
The unit can be optionally mounted to 35x15mm, T-
type DIN rails using optional ST130-DIN DIN-rail mounting adapter kit.
Refer to the Mounting & Dimensions section for more details.
Shipping Weight:
0.5 pounds (0.22 Kg) packed.
Safety Approvals:
Model ST132-0610 is UL Listed (USA & Canada)
suitable for use in Class I, Division 2, Groups A, B, C, D Hazardous
Locations, or Nonhazardous Locations only.
ATEX Certified:
Model ST132-0610 is ATEX Certified for Explosive
Atmospheres per ATEX Directive 94/9/EC which complies with standards
BS EN 60079-0:2012 & BS EN 60079-15:2010.
II 3 G Ex nA IIC T4 Gc -40
o
C
≤ Ta ≤ +80
o
C
DEMKO 13 ATEX 1113348X
X = Special Conditions
1) Must be installed in an ATEX Certified enclosure with a minimum
ingress protection rating of at least IP54 and used in an environment
of not more than pollution degree 2.
2) Enclosure must have a door or cover accessible only by the use of a
tool.
3) Provisions shall be made to prevent the rated voltages from being
exceeded by the transient disturbances of more than 140% of the
peak rated voltage.
Environmental
These limits represent the minimum requirements of the applicable
standard, but this product has typically been tested to comply with higher
standards in some cases.
Operating Temperature:
-40
C to +80
C (-40
F to +176
F).
Storage Temperature:
-40
C to +85
C (-40
F to +185
F).
SPECIFICATIONS
Enclosure and Physical
Agency Approvals
ATEX Certified
Environmental