microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 5 -
http://www.acromag.com
- 5 -
https://www.acromag.com
Key Features
•
High-Density 22.5mm wide enclosure mounts on standard DIN rails and
includes pluggable, front-facing terminals. Front-panel LED indicators for
Bluetooth wireless technology link, power, and relays aide trouble-shooting.
•
Field-pluggable microBlox
®
input modules (sold separately) allow you to
change input types on this carrier, usually without recalibration. Modules are
over-molded and RoHS compliant, and offer superior shock, moisture, and
dust protection.
•
Channel has dual alarm outputs that is configured using Bluetooth wireless
technology. Two alarm carrier models are available
—
one with mechanical
relays (5A/250VAC/30VDC), one with solid-state relays (1A/200Vpk AC/DC).
•
Free Bluetooth wireless technology C
onfiguration App with Android™ or iOS™
support, no additional software required.
•
16-character Password Protection for Bluetooth wireless technology access.
•
Designed, hardened, and thoroughly tested for use in Harsh Environments.
•
CE Approved & UL/cUL Class I, Division 2 Approvals.
•
FCC Conformity Class B.
•
ATEX / IECEx Certified for Explosive Atmospheres:
II 3 G Ex nA nC* IIC T4 Gc -40
o
C
≤
Ta
≤
+75
o
C (* for Model uBTA-H-1MR)
DEMKO 18 ATEX 2086X and IECEx UL 18.0092X
•
Designed and manufactured for High Quality/High Reliability with AS9100
(Aerospace Quality)/ISO9001.
•
Carrier includes both 0-5V/1-5V and 0-20mA/4-20mA transmitter outputs.
•
Better than ±0.1% alarm and transmitter output accuracy.
•
Wide ambient temperature operation from -40°C to +75°C.
•
All I/O and power ports are transient protected.
•
Wide-range DC powered from 6-32V and Bus Power Ready for optional clean
wired power along the DIN Rail and/or Redundant Power Connection.
•
High 1500VAC Safety Isolation: Field input, transmitter output, power, and
relay contacts (including between contacts) are individually isolated for
common-mode voltages up to 250VAC, or 354V DC off DC power ground, on a
continuous basis (will withstand 1500VAC HIPOT/dielectric strength test for
one minute without breakdown). This complies with test requirements of
ANSI/ISA-82.01-1988 for voltage rating specified.
•
High Shock & Vibration Immunity - Conforms to: IEC 60068-2-6: 10-500 Hz,
5G, 2 Hours/axis, for sinusoidal vibration; IEC 60068-2-64: 10-500 Hz, 5G-rms,
2 Hours/axis, for random vibration, and IEC 60068-2-27: 30G, 11ms half-sine,
18 shocks at 6 orientations and 50G, 3ms half-sine, 18 shocks at 6
orientations, for mechanical shock.
•
EMC (Electromagnetic Compatibility)
–
Min Immunity per BS EN 61000-6-1
(2007); CE marked, per EMC Dir
•
2014/30/EU. Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2;
Radiated Field Immunity (RFI), per IEC 61000-4-3 and ETSI EN 301 489;
Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4; Surge Immunity,
per IEC 61000-4-5. Conducted RF Immunity (CRFI), per IEC 61000-4-6.
•
Low Emissions - This is a Class B Product with Emissions per BS EN 61000-6-3
(2007+A1:2011) and Spurious Emissions per ETSI EN 300 328. Enclosure Port,
per CISPR 16. Low Voltage AC Mains Port, per CISPR 16.
•
Installation Category - Suitable for installation in a Pollution Degree 2
environment with an Installation Category (Over-voltage Category) II rating
per IEC 1010-1 (1990).