microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 28 -
http://www.acromag.com
- 28 -
https://www.acromag.com
Environmental
Electromagnetic Compatibility (EMC)
Minimum Immunity per BS EN 61000-6-1:
1)
Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2.
2)
Radiated Field Immunity (RFI), per IEC 61000-4-3.
3)
Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4.
4)
Surge Immunity, per IEC 61000-4-5.
5)
Conducted RF Immunity (CRFI), per IEC 61000-4-6.
This is a Class B Product with Emissions per BS EN 61000-6-3:
1)
Enclosure Port, per CISPR 16.
2)
Low Voltage AC Mains Port, per CISPR 14, 16.
3)
DC Power Port, per CISPR 16.
4)
Telecom / Network Port, per CISPR 22.
Agency Approvals
Electromagnetic Compatibility (EMC
): CE Marked, per EMC Directive
2014/30/EU.
FCC Conformity:
This device complies with Part 15, Class B of the FCC rules.
Safety Approvals:
UL Listed (USA & Canada). Hazardous Locations
–
Class I,
Division 2, Groups A, B, C, D Hazardous Location or Nonhazardous Locations
only. These devices are open panel type circuits that are intended to be
installed in an enclosure suitable for the environment.
ATEX / IECEx Certified:
Model uBTA-P-1 carries are ATEX Certified for Explosive
Atmospheres per ATEX Directive 2014/34/EU which complies with standards IEC
60079-0 Edition 6, IEC 60079-15 Edition 4, EN 60079-0:2012+A11:2013, and
EN 60079-15:2010.
II 3 G Ex nA nC IIC T4 Gc -40
o
C
≤
Ta
≤
+75
o
C (For model uBTA-H-1MR only)
II 3 G Ex nA IIC T4 Gc -40
o
C
≤
Ta
≤
+75
o
C (For all other models)
DEMKO 18 ATEX 2086
X
IECEx UL 18.0092
X
X
= Special Conditions:
1) The equipment shall only be used in an area of not more than pollution
degree 2, as defined in EN/IEC 60664-1.
2) The equipment shall be installed in an enclosure that provides a degree of
protection not less than IP 54 and only accessible with the use of a tool in
accordance with EN/IEC 60079-15.
3) Transient protection shall be provided set to a level not exceeding 140% of
the peak rated voltage value at the supply terminals to the equipment.
Reliability Prediction
Reliability Prediction
MTBF (Mean Time Between Failure):
MTBF in hours using MIL-HDBK-217F,
FN2.
Per MIL-HDBK-217, Ground Benign, Controlled, G
B
G
C
uBTA-H-1x
MTBF (Hours)
MTBF (Years)
Failure Rate (FIT)
25°C
TBD hrs
TBD years
TBD
40°C
TBD hrs
TBD years
TBD
uBTX-H-1
MTBF (Hours)
MTBF (Years)
Failure Rate (FIT)
25°C
TBD hrs
TBD years
TBD
40°C
TBD hrs
TBD years
TBD