microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 27 -
http://www.acromag.com
- 27 -
https://www.acromag.com
Power
w/uB42 uBTA-H-1MR
uBTA-H-1SR
uBTX-H-1
POWER
1.54W
1.29W
1.15W
SUPPLY
Fully Loaded Current Draw w/uB42
6V
257mA
215mA
192mA
9V
171mA
143mA
128mA
12V
128mA
108mA
96mA
15V
102mA
86mA
77mA
24V
64mA
54mA
48mA
32V
48m
40mA
36mA
Power Supply Effect:
Less than
0.001% of output span effect per volt DC
change.
Enclosure & Physical
General purpose plastic enclosure
with an integrated DIN clip for
mounting on 35mm “T
-
type” DIN
rail.
Dimensions
: Width = 22.5mm (0.9 inches), Length = 114.5mm (4.51 inches),
Depth = 99.0mm (3.90 inches without module plugged in). Refer to Mechanical
Dimensions drawing. Note that the plug-in module adds approximately 14mm
(0.55”) to the vertical depth
of the plastic enclosure mounted on a DIN rail.
I/O Connectors:
Includes removable plug-in type terminal blocks rated for
12A/250V; AWG #26-14 stranded or solid copper wire.
Case Material:
Self-extinguishing polyamide, UL94 V-0 rated, color light gray.
General purpose NEMA Type 1 enclosure.
Circuit Board:
Military grade fire-retardant epoxy glass per IPC-4101/98.
DIN-Rail Mounting:
Unit is normally mounted to 35x15mm, T-type DIN rails.
Refer to the DIN Rail Mounting & Removal section for more details.
Unit Weight:
0.35 pounds (0.16 Kg).
Environmental
These limits represent the minimum
requirements of the applicable
standard, but this product has
typically been tested to comply with
higher standards in some cases
Operating Temperature:
-40
C to +75
C (-40
F to +158
F).
Storage Temperature:
-40
C to +85
C (-40
F to +185
F).
Relative Humidity:
5 to 95%, non-condensing.
Isolation
: Input (field) isolation is provided by the input module. The input, the
carrier transmitter outputs (together), carrier power, and the relay outputs
(including contact-to-contact) are all isolated from each other for common-
mode voltages up to 250VAC, or 354V DC off DC power ground, on a continuous
basis (will withstand 1500VAC dielectric strength test for one minute without
breakdown). This complies with test requirements of ANSI/ISA-82.01-1988 for
voltage rating specified.
Installation Category:
Suitable for installation in a Pollution Degree 2
environment with an Installation Category (Over-Voltage Category) II rating per
IEC 1010-1 (1909).
Shock & Vibration Immunity:
Conforms to: IEC 60068-2-6: 10-500 Hz, 4G, 2
Hours/axis, for sinusoidal vibration; IEC 60068-2-64: 10-500 Hz, 4G-rms, 2
Hours/axis, for random vibration, and IEC 60068-2-27: 25G, 11ms half-sine, 18
shocks at 6 orientations, for mechanical shock.