microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 14 -
http://www.acromag.com
- 14 -
https://www.acromag.com
Transmitter Output Connections
This carrier includes both 0-20mA current
(550Ω max)
, and 0-5V
voltage (1KΩ min)
transmitter output connections at TB4 as shown below. Output voltage is driven
directly by the plug-in module, while the carrier includes a voltage to current
converter to also output 0-20mA DC for 0-5V driven by the module. The
simultaneous current and voltage outputs are not isolated from each other and
share common. This output circuit is normally earth grounded at the output
common terminal as shown below.
Note
–
For 4-20mA Transmitter Output
: The alarm carrier normally requires that
the input module scales its input range to 0-5V for use on this carrier, and this
will drive 0-
20mA at the carrier’s current output. If your application requires a 4
-
20mA current output, you may use the I/O Scaling function of the Agility mobile
app to scale your module’s input range to 1
-5V output instead of 0-5V, and this
will produce 4-20mA from the alarm carrier (note that the tandem voltage output
of the carrier also becomes 1-5V, not 0-5V). The Agility App can also scale this for
you if you select 4-20mA as an output type option under the uBTA Alarm tab.