microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 11 -
http://www.acromag.com
- 11 -
https://www.acromag.com
Input Connections, BLE Jumper, and CJC Jumper
A single MicroBlox input module plugs directly into the front panel opening of this carrier and is retained by
an internal spring clip. Input connections are wired to the carrier terminals in the same fashion as input
connections to uB modules when mounted on uB back-panels (refer to your uB manual per specific model).
Wired jumpers are also used on this carrier to enable BLE linking and CJC connections, and have the same
effect as setting the standard uB backpanel BLE and CJC switches (a jumper present equals switch ON).
Observe proper polarity when making input connections. TB1 of this carrier connects INPUT ±, while TB2
connects EXC ±. The last two terminals of TB1 are for installation of a CJC jump-wire to enable CJC for some
input models (see table above) and this has the equivalent function of the CJC DIP switch of uB back-panels.
Similarly, TB2 includes two jumper terminals to enable Bluetooth wireless technology linking (refer to your uB
model instructions) and adding this jumper is equivalent to switching the BLE DIP switch of uB back-panels
ON. Refer to the table above and add or remove this jump-wire between the last two terminals of TB1
—
some
modules will require a CJC connection, while others do not. Installing a jump wire between the first two
terminals of TB2 will enable you to link to the installed uB module using Bluetooth wireless technology from
your smartphone or tablet (remove this jumper to block access). Refer to the figure above and your specific
uB module manual (see below) for info on making input connections, or for information about CJC jumper
installation, or enabling Bluetooth wireless technology linking:
REFERENCE
DESCRIPTION
8501-037
uB31 & uB41 Voltage Input User Manual
8501-040
uB30 & uB40 mV Input User Manual
8501-041
uB32 DC Current Input User Manual
8501-042
uB42 DC Current Input w/2-Wire Excitation User Manual
8501-043
uB34 2/3-Wire & uB35 4-Wire RTD Input User's Manual
8501-044
Introduction to Agility Configuration Tool for microBlox®
8501-047
uB37 & uB47 TC Input User Manual
8501-050
uB04/uB08/uB16 Back-Panel User Manual