microBlox® Transmitter/Alarm Carrier
Model uBTA-H-1MR/uBTA-H-1SR/uBTX-H-1
Acromag, Inc. Tel: 248-295-0880
- 10 -
http://www.acromag.com
- 10 -
https://www.acromag.com
Power
Connections…
IMPORTANT
–
End Stops:
If this module uses optional bus power, or is redundantly powered via
the DIN rail bus, then for hazardous location installations (Class I, Division 2 or ATEX Zone 2) it
must also use two end stops to help secure the terminal block and module assembly to the DIN
rail (Acromag part 1027-222 not shown but included in XTBUS-KIT).
IMPORTANT - Fusing:
It is recommended that supplies capable of delivering more than 2.5A of
power to the carrier (or bussed carriers) be fused with a surge tolerant fuse. Unit includes a
transient voltage suppressor clamp across its power input that will clamp transient overvoltage
conditions. A sustained over-voltage condition from an unfused power supply could drive
excessive fault current flow in the circuit that can damage the carrier if allowed to exceed 3A.