Acromag IntelliPack 811T Series User Manual Download Page 6

IntelliPack Series 811T Transmitter/Alarm User's Manual                                                   DC Voltage/Current Input 
__________________________________________________________________________________________ 

 - 6 - 

 
1.

    Power:

  Refer to Electrical Connections Drawing 4501-640.  

Variations in power supply voltage within rated limits has 
negligible effect on module accuracy.  For supply 
connections, use No. 14 AWG wires rated for at least 75

C.  

The power terminal is diode-coupled for reverse polarity 
protection. 

 
2.

   DC Voltage/Current Inputs (Without AC Current Sensor):  

Connect input(s) per Drawing 4501-640.  Observe proper 
polarity (see label for input type).  An excitation supply is 
provided at the input for powering two-wire transmitters. 

 
3.

   AC Current Input (Optional):

  Refer to Drawing 4501-633 to 

connect the optional AC current sensor.  The sensor is 
typically mounted near the AC current being measured and 
will transmit a low level DC milliampere signal to the module.  
This allows the module to be mounted remote from the AC 
signal and sensor and connected using small gauge wire.  
The sensor output (Red/Black) wires can be shorted, open-
circuited, or removed from the transmitter input terminals, 
without hazard to personnel or to the sensor. 

 

AC Current Sensor:

  Per Table 2 on Page 4, loop the 

required number of turns through the toroid for the full-scale 
current range required by your application.  Use the cable tie 
provided with the sensor to mechanically secure it. 
 

DANGER:

  If the AC current sensor is used with an AC 

Current Transformer (C.T.), disconnect power from the 
C.T., or short the output of the C.T., before removing the 
wire going through the AC current sensor.  If this is not 
done, an open circuited C.T. will generate hazardous high 
voltages and possible C.T. damage.

 

 
4.

   Analog Output Connections

:  Wire outputs as shown in 

Electrical Connections Drawing 4501-640.  For voltage 
output, you must also install a jumper between the output “I+” 
and “JMP” terminals (pre-installed from the factory).  Remove 
this jumper for current output. 

 
5.

   Output Relay Contacts (811T-1500)

:  Wire relay contacts as 

shown in Electrical Connections Drawing 4501-640.  See the 
“Alarm Relay Specifications” for power capacity.  If 
necessary, an interposing relay can be used to switch higher 
currents as shown in Interposing Relay Connection Drawing 
4501-646. 

 

Electromechanical Relay Contact Protection:

  To 

maximize relay life with inductive loads, external protection is 
required.  For DC inductive loads, place a diode across the 
load (1N4006 or equivalent) with cathode to (+) and anode to 
(-).  For AC inductive loads, place a Metal Oxide Varistor 
(MOV) across the load.  See Relay Contact Protection 
Drawing 4501-646 for details. 

 

IMPORTANT:

  Noise and/or jitter on the input signal has the 

effect of reducing (narrowing) the instrument’s deadband and 
may produce contact chatter.  The long term effect of this will 
reduce the life of mechanical relays.  To reduce this 
undesired effect, you should increase the effective deadband.  
Note that the input averaging function of this transmitter may 
also be used to reduce contact chatter.  The configurable 
relay time delay may also help eliminate relay chatter. 

 
6.

   Grounding:

  See Electrical Connections Drawing 4501-640. 

The module housing is plastic and does not require an earth 
ground connection.  However, there are mounting positions 
on the input and output terminals to connect cable shields, 
plus earth ground.  These connections are isolated from the 
internal circuit and are recommended to minimize noise and 
help protect the unit from damaging I/O transients. 

 

WARNING:

  For compliance to applicable safety and 

performance standards, the use of shielded cable is 
recommended as shown in Drawing 4501-640.  Further, the 
application of earth ground must be in place as shown in 
Drawing 4501-640.  Failure to adhere to sound wiring and 
grounding practices may compromise safety & performance.

 

 
 

3.0  MODULE CONFIGURATION 

 

This transmitter/alarm module needs to be configured for 

your application.  Configuration is done using Acromag’s 
Windows 95/98/ME/NT/XP/2000 IntelliPack Configuration 
Program and Serial Port Adapter.  Transmitter configuration 
details are included in the IntelliPack Transmitter Configuration 
Manual (8500-570).  Field configuration of transmitter zero & full-
scale, plus setpoint & dropout (811T-

1500 units), via the module’s 

push-

buttons and LED’s is covered below. 

 

FIELD CONFIGURATION 

 

This program mode allows adjustment to key transmitter 

configuration and alarm parameters in the field, without having to 
connect a host computer.  Field reprogrammability of zero & full-
scale (scaling parameters), plus alarm setpoint & deadband 
(Model 811T-1500) is accomplished via the transmitter/alarm 
module’s “SET”, “MODE”, “UP”, and “DOWN” push buttons, and 
the zero/full-

scale and relay LED’s (see Drawing 4501-642). 

 
Equipment Required 

 

 

An accurate input source (voltage or current) adjustable over 
the configured input range.  This source must be accurate 
beyond the module specifications for best results.  For 
voltage inputs, use a voltage source with an output 
impedance of 100

 or less. 

 

An accurate current or voltage meter is also required to 
monitor the output level.  This meter must be accurate 
beyond the module specifications for best results. 

 

Note:

  

The module’s input range must already be set via the 

IntelliPack Configuration Software.  Input levels outside of 
the configured input range will not be accepted for zero, full-
scale, setpoint, or dropout calibration.  Since input levels 
cannot be validated during field programming, entering 
incorrect signals can produce an undesired output response. 
Install a jumper between the output “I+” and “JMP” terminals 
for voltage output.  Remove this jumper for current output. 

Summary of Contents for IntelliPack 811T Series

Page 1: ...rms Process Current Voltage Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA Da...

Page 2: ...factory overall system design It is agreed between the Buyer and Acromag that this is the Buyer s responsibility 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter mod...

Page 3: ...applications Custom IntelliPack module configurations are also possible please consult the factory Key IntelliPack 811T Features Agency Approvals cULus Listed Easy Windows Configuration Fully reconfig...

Page 4: ...transparent to the user It receives its power from the IntelliPack module The adapter has a DB9S connector that mates to the common DB9P serial port connector of a host computer The adapter also has a...

Page 5: ...r NT Configuration Program and Serial Port Adapter Configuration is normally done prior to field installation since field configurability via the module s push buttons is generally limited to zero ful...

Page 6: ...wing the instrument s deadband and may produce contact chatter The long term effect of this will reduce the life of mechanical relays To reduce this undesired effect you should increase the effective...

Page 7: ...rease the amount of increment or decrement 10 Press the SET push button to accept the full scale value Note that every time the SET button is pressed the yellow Status LED will flash once and the full...

Page 8: ...ks and calibrates the performance of each module Please refer to Acromag s Service Policy Bulletin or contact Acromag for complete details on how to obtain service parts and repair PRELIMINARY SERVICE...

Page 9: ...itation current of process current inputs Input Filter Normal mode filtering plus digital filtering optimized and fixed per input range within the ADC Noise Rejection Normal Mode 40dB 60Hz typical wit...

Page 10: ...rail mountable for flexible high density approximately 1 wide per unit mounting See Enclosure Dimensions Drawing 4501 642 for details Dimensions Width 1 05 inches Height 4 68 inches Depth 4 35 inches...

Page 11: ...Relay Yellow Constant ON indicates alarm condition for relay During field configuration this LED has a different function see below Field Configuration Mode Run Green Turned OFF in this mode Status Ye...

Page 12: ...the effect of reducing narrowing the instrument s deadband and may produce contact chatter Another long term effect of contact chatter is a reduction in the life of the mechanical relay contacts To re...

Page 13: ...L TIPL EXER AND CONDITIONING INPUT SIGNAL 1 6 BIT A D SHL D SHIEL D ISOL ATION RTN INPUT I 2 3 2 4 2 5 V 2 2 MODEL 811T 1500 UNIT ONLY REL AY REL AY ISOL ATION 4 5 COM N O RELAY 4 6 SHL D NC 4 3 4 4 N...

Page 14: ...ation S oftware or Module P ush B uttons LIMIT A LA RM Transfer Functions Linear P roportional S quare Root Linearizer ON OFF A larm On Off K 1 A nalog OUTP UT type ALARM OUTPUT BLOCK A larm Configura...

Page 15: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 15...

Page 16: ...TB2 2 2 V 2 3 I 2 4 RTN I NPUT SHLD 2 5 2 6 EARTH G RO UND TB2 M O D E M O DE SW I TCH Z F S ZERO FUL L SCAL E L ED YEL L O W Acr om ag R U N RUN PW R L ED G REEN STATUS L ED YEL L O W R L Y S T REL...

Page 17: ...GROUND L OOP TO GROUND AS THIS WOUL D PRODUCE INPUTS GROUND ONL Y ONE INPUT DO NOT CONNECT THE SECOND INPUT P A S S I NG T H ROUGH C E N T E R H OLE S E E I NP U T RA NGE S E LE C T I ON T A B LE A C...

Page 18: ...TACT 42 34 SPDT CONTACTS PROTECTION AC RELAY POWER DIODE DC RELAY POWER PROTECTION FIGURE A CONTACT SPDT CONTACTS INPUT CONNECTIONS TB1 OUTPUT JUMPER I TO JMP FOR VOLTAGE OUT POWER 8XXT 1500 RELAY OUT...

Page 19: ...____________________________________ 19 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R A...

Page 20: ...__________________________________________ 20 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 K CAP...

Page 21: ...IntelliPack Series 811T Transmitter Alarm User s Manual DC Voltage Current Input __________________________________________________________________________________________ 21 Notes...

Reviews: