LED Indicators (Front-Panel)
Power PWR (Green)
–
Channel Green ON indicates power is applied to unit (this LED
is sourced from isolated internal 3.3V rail).
Fault FLT - Channel Output (Orange, Each Output, FLT1 & FLT2) -
Orange FLT LED per
current output channel. ON indicates channel current output is open circuit, or the
corresponding current output load resistance is too high to drive accurate current to
it (load resistance is greater than 525
Ω).
ON may also indicate over-temperature if
the output driver die temperature has exceeded 142°C.
Environmental
These limits represent the
minimum requirements of the
applicable standard, but this
product has typically been tested
to comply with higher standards in
some cases.
Operating Temperature:
-40
C to +70
C (-40
F to +158
F). It is recommended this
unit be mounted upright on a DIN rail, allowing free air to flow into the bottom vent,
pass through the unit and out the top vent.
Storage Temperature:
-40
C to +85
C (-40
F to +185
F).
Relative Humidity:
5 to 95%, non-condensing.
Altitude:
Up to 2000 meters.
Isolation:
Input 1/USB, input 2, output 1, output 2, and DC power circuits are
isolated from each other for common-mode voltages up to 250VAC, or 354V DC off
DC power ground, on a continuous basis (will withstand 1500VAC dielectric strength
test for one minute without breakdown). Complies with test requirements of UL
61010C-
1 First Edition, August 9, 2002 “UL Standard for Safety for Process Control
Equipment”
for the voltage rating specified.
Operating Shock & Vibration Immunity:
Designed to comply with IEC 60068-2-6: 10-
500Hz, 4G, 2 hours/axis, for random vibration, and IEC 60068-2-27: 25G, 11ms half-
sine, 18 shocks at 6 orientations, for mechanical shock.
Installation Category:
Suitable for installation in a Pollution Degree 2 environment
with an Installation Category (Over-voltage Category) II rating per IEC 1010-1 (1990).
2014/30/EU Electromagnetic Compatibility (EMC)
Minimum Immunity per BS EN 61000-6-2:
1)
Electrostatic Discharge Immunity (ESD), per IEC 61000-4-2.
2)
Radiated Field Immunity (RFI), per IEC 61000-4-3.
3)
Electrical Fast Transient Immunity (EFT), per IEC 61000-4-4.
4)
Surge Immunity, per IEC 61000-4-5.
5)
Conducted RF Immunity (CRFI), per IEC 61000-4-6.
This is a Class A Product with Emissions per BS EN 61000-6-4:
1) Enclosure Port, per CISPR 16.
2) Low Voltage AC Mains Port, per CISPR 14, 16.
Agency Approvals
Electromagnetic Compatibility (EMC
): CE marked, per EMC Directive 2014/30/EU.
FCC Conformity:
This device complies with Part 15, Class A of the FCC rules.
Safety Approvals:
cULus Listed Class I, Division 2, Groups A, B, C, D Hazardous
Location or Nonhazardous Locations only. These devices are open-type devices that
are to be installed in an enclosure suitable for the environment. Consult Factory.
ATEX/IECEx Certified:
ATEX/IECEx Certified for Explosive Atmospheres per ATEX
Directive 2014/34/EU which complies with standards EN IEC 60079-0:2018, EN
IEC 60079-7:2015 +A1:2018, IEC60079-0 Edition 7, and IEC 60079-7 Edition 5.1.
II 3 G Ex ec IIC T5 Gc -40
o
C
≤
Ta
≤
+70
o
C
UL 20 ATEX 2416
X
IECEx UL 20.0088
X
X
= Special Conditions
1)
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in EN/IEC
60664‐1.