Acromag 655T Series User Manual Download Page 6

Series 655T/656T Transmitter User's Manual                                                                                          mV/TC Input 
___________________________________________________________________________________________ 
 

 - 6 - 

 

Refer to the Table 4 of the following page when using a 
precision millivoltage source to configure the zero and full-
scale input range endpoints (with CJC turned Off). 

 

Transmitter Zero/Full-Scale Configuration Procedure 

 
1.     Set DIP switch 12 of the channel to the up/ON or “Unlock” 

position to allow the front panel toggle switches to make 
adjustments to zero and full-scale. 

2.     Connect a precision voltage source or thermocouple 

calibrator to the input, as required.  Connect a current 
milliampmeter (in series with the loop), or voltmeter (across 
a precision load resistor), to accurately read the output 
signal.  Apply power to the transmitter. 

3.     Adjust the input source to the zero level (this level must be 

within the input range selected).  For our example: use 0

C. 

4.     If the measured output is not precisely at zero (4.000mA), 

depress the 

Zero

 

“Z” toggle switch to the 

“UP”

 

or “

DN

” 

position as required, to precisely adjust the output current to 
4.000mA. 

Note:  The Zero Up/Down toggle functions as a trim 
adjustment for the zero output loop current level.  
Successive depressions of the “UP” or “DN” toggle positions 
will increment or decrement the output current by a small 
amount, while holding the toggle switch in the “UP’ or “DN” 
position will increase the amount of increment or decrement.  
Reverse Acting Outputs:

  A reverse acting output can be 

easily obtained by using the Up/Down toggle to adjust the 
output level accordingly.  For a reverse acting output, you 
would adjust the zero output level to a higher level here 
(20.000mA) in response to the zero input, and a lower level 
(4.000mA) in response to a full-scale input signal (step 6). 

5.     Adjust the input source to the full-scale level (the input value 

must be within the input range selected).  For our example: 
use 200

C. 

Note:  The full-scale input value must be greater than the 
zero input value.  If the zero and full-scale points are too 
close together, performance will be degraded. 

6.     If the output is not exactly at the full-scale level (20.000mA), 

press the 

Full-Scale

 

“FS” Up/Down toggle to the 

“UP”

 or 

“DN”

 position, as required to precisely adjust the output 

current to 20.000mA.  

Note:  The FS Up/Down toggle functions as a trim 
adjustment for the full-scale output loop current level.  
Successive depressions of the “UP” or “DN” toggle positions 
will increment or decrement the output current by a small 
amount, while holding the toggle switch in “UP’ or “DN” 
position will increase the amount of increment or decrement.  
Reverse Acting Outputs:

  A reverse acting output can be 

easily obtained by using the Up/Down toggle to adjust the 
output level accordingly.  For a reverse acting output, you 
would adjust the output level to a lower level (4.000mA) in 
response to the full-scale input here, and a higher level 
(20.000mA) in response to a zero input signal (step 4). 

7.     After completing zero and full-scale adjustment, be sure to 

return DIP switch 12 to the down or “Lock” position after 
waiting at least 15 seconds.  This will help prevent 
inadvertent reconfiguration or tampering in the field by 
locking out adjustment via the front panel zero and full-scale 
toggle switches.  Repeat this procedure for the second 
channel of dual channel units.   

 

IMPORTANT:

  Note that the zero and full-scale adjustments 

take effect immediately and are saved to non-volatile 
memory after 15 seconds of toggle switch inactivity.  Please 
wait at least 15 seconds following adjustment before 
powering down or setting DIP switch 12 to the “Lock” 
position or your new configuration settings will be lost.

 

 
After setting the DIP switches as required by your application 

and configuring zero and span, be sure to install the plastic 
cover(s) over the DIP switch openings.  To install these covers, 
you will have to remove the left side cover by prying at each 
corner with a screwdriver, then sliding the DIP switch covers into 
the switch opening.  Replace the left side cover by snapping it 
into place and applying pressure at each corner to secure. 
 
 

4.0  THEORY OF OPERATION 

 

Refer to Simplified Schematic 4501-777 to gain a better 

understanding of the circuit.  A portion of the output loop current 
is routed to a transformer while being driven in an alternating 
push-pull fashion to generate an input supply.  The remaining 
output current is pulled through a current steering circuit that 
regulates the loop current based on an optically coupled input 
signal.  The transmitter will accept a thermocouple or voltage 
input, and condition it to a voltage signal for the A/D converter.  A 
reference temperature sensor signal voltage is also input to the 
A/D.  The A/D converter stage then applies appropriate gain to 
these signals, performs analog-to-digital conversion, and digitally 
filters the signals.  The digitized signals are then transmitted 
serially to a microcontroller.  The microcontroller completes the 
transfer function according to the input type and configuration, 
and sends a corresponding output signal to an optocoupler and 
filter circuit.  A corresponding analog output voltage is generated 
and used to drive the amplifier used to modulate the loop current.  
The embedded configuration and calibration parameters are 
stored in non-volatile memory integrated within the micro-
controller. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Summary of Contents for 655T Series

Page 1: ...itters mV TC Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 2000 Acromag Inc Printed in the USA Data and specific...

Page 2: ...tions Output Enclosure Approvals1 Factory Configuration2 655T 06003 C 656T 06003 C 656T E600 C Notes Table 1 1 Approvals cULus Listed Hazardous Locations Class I Division 2 Groups A B C D See specific...

Page 3: ...SE UNPACKING AND INSPECTION Upon receipt of this product inspect the shipping carton for evidence of mishandling during transit If the shipping carton is badly damaged or water stained request that th...

Page 4: ...nsmitter accuracy Ripple Noise Power supply ripple at 60Hz 120Hz is normally reduced at the load by the transmitter The ripple at the load will generally be less than 0 02 of span per volt peak to pea...

Page 5: ...switch 12 must be set ON to unlock the front panel Z FS toggle switches After setting the DIP switches as required for your application you may optionally re scale your input range to the output 4mA a...

Page 6: ...of increment or decrement Reverse Acting Outputs A reverse acting output can be easily obtained by using the Up Down toggle to adjust the output level accordingly For a reverse acting output you woul...

Page 7: ...20 878 18 504 13 008 1800 13 585 5 0 SERVICE AND REPAIR CAUTION Risk of Electric Shock More than one disconnect switch may be required to de energize the equipment before servicing SERVICE AND REPAIR...

Page 8: ...pecifications Thermocouple User configured for the eight types of thermocouples shown in Table 5 Model 656T E600 units only support J K TC types plus the 0 125mV input range Linearization separately e...

Page 9: ...igible line drop At a 24V DC supply Rload 0 600 Note For sensitive applications with high speed acquisition rates high frequency noise may be reduced considerably by simply placing a 0 1uF capacitor d...

Page 10: ...DN direction to lower the full scale output level NOTE Note that the zero and full scale adjustments take effect immediately and are saved to non volatile memory after 15 seconds of toggle switch inac...

Page 11: ...OOPS AND MEASUREMENT ERROR NOTE 1 SHIELDED CABLE 4 20mA NOTE 1 WARNING TB2 or TB3 Acromag CHAN 1 DC SUPPLY 12 36V DC SOURCE VOLTAGE DC SUPPLY 4 20mA SHIELDED CABLE 12 36V DC INPUT CHAN 2 TB2 or TB3 MO...

Page 12: ...tionON Lock ON 8 9 10 11 12 ConfigurationUNLOCKED 1 ConfigurationLOCKED LinearizationOFF LinearizationON 0 0 1 0 0 1 0 0 1 0 0 0 1 1 1 1 1 1 1 0 1 1 0 1 1 0 0 0 0 0 0 1 1 0 0 CJC OFF CJC ON TC Break D...

Page 13: ...___________________________________________________________ 13 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision...

Page 14: ...Series 655T 656T Transmitter User s Manual mV TC Input ___________________________________________________________________________________________ 14 Notes...

Reviews: