Acrel ASJ Series Installation And Operation Instruction Manual Download Page 17

14 

CRC check code: the error check (CRC) field takes up two bytes and contains a 16 bit binary 

value. The CRC value is calculated by the transmitting device, and then attached to the data frame. 

The receiving device recalculates the CRC value when receiving byte data, and then compares it 

with the value in the received CRC field. If the two values are not equal, an error occurs. 

The process of generating a CRC is as follows: 

1)  Reset a 16-bit register as 0xFFFF (all 1), which is called CRC register. 

2)  The 8-bit of the first byte in the data frame is XOR with the low byte in CRC register, and 

the result is saved back to CRC register. 

3)  Move the CRC register to the right by one bit, fill the highest bit with 0, and the lowest bit 

is out and detected. 

4)  If the lowest bit is 0, repeat the third step (the next shift); if the lowest bit is 1, XOR the 

CRC register with a preset fixed value (0xa001). 

5)  Repeat the third and fourth steps until eight shifts, this completes a complete octet. 

6)  Repeat steps 2 through 5 to process the next octet until all bytes are processed. 

7)  The final CRC register value is the value of the CRC. 

In addition, there is a method to calculate CRC by using the preset table. Its main feature is that 

the calculation speed is fast, but the table needs a large storage space. This method will not be 

described here, please refer to the related materials. 

8.2 Introduction to function code 

8.2.1 Function code 03H or 04H: register read 

This function allows users to obtain data and system parameters collected and recorded by the 

device.  There  is  no  limit  to  how  much  data  a  host  can  request  at  a  time,  but  it  cannot  exceed  the 

defined address range. 

The following example reads a value from machine 01 at the address 0008H. 

Master Send 

Data 

 

 

Slave Return 

Data 

Address 

01H 

 

 

Address 

01H 

Function 

03H 

 

 

Function 

03H 

Start Address 

High byte 

00H 

 

 

Bytes 

02H 

Low byte 

08H 

 

  Data of 

Registers 

High byte 

00H 

number of 

Registers 

High byte 

00H 

 

 

Low byte 

50H 

Low byte 

01H 

 

 
CRC codes 

Low byte 

21H 

CRC codes 

Low byte 

74H 

 

 

High byte 

75H 

High byte 

0CH 

   

 

 

7.2.2 Function code 10H: write register 

Function code 10H allows the user to change the contents of multiple registers. The time and 

date in the meter can be written with this function number. The master can write up to 16 (32 bytes) 

of data at a time. 

The following example is a device with a preset address of 01 date and time of 12:00 on Friday, 

December 01, 2009.From Monday to Sunday, 1 to 7 are used instead. 

 

Summary of Contents for ASJ Series

Page 1: ...041 ASJ Series Residual Current Operated Relay Installation and Operation Instruction V1 9 Acrel Co LTD...

Page 2: ...tions in this operation manual and Acrel does not take responsibility for personal injuries or economic losses caused by ignoring tips of this manual The contents of the manual will be continuously up...

Page 3: ...ing attention 4 5 Operating Guide 5 5 1 Description of AC type Panel 5 5 2 Description of A type panel 5 5 3 Description of LCD type panel 5 5 4 Description of Selection 6 5 5 Instructions for the sel...

Page 4: ...Rated residual operating current can be measured Limit non driving time can be set Two sets of relay output With local and remote test and reset functions Guide DIN 35mm ASJ10 LD1A A type residual cu...

Page 5: ...0 0 06 0 1 0 2 0 3 0 5 0 8 1 4 10 s note 4 Rated residual non operating current I no 50 I n 50 I n Performance characteristics Sinusoidal AC Sinusoidal AC and pulsating DC Frequency 50Hz 5Hz 50Hz 5Hz...

Page 6: ...1 Installation Steps ASJ20 series instrument installation method is panel installation both sides of the buckle extrusion fixed the specific operation is as follows 1 On the switchboard choose the ap...

Page 7: ...xiliary power supply and signal input terminal Auxiliary power supply Signal input 4 3 2 Switching quantity input output terminal DI1 DI2 COM1 24 25 33 Relay output terminal Switching input terminal n...

Page 8: ...t button To reset the system 3 Alarm light Lights when the rated residual operating current I n is exceeded 4 Test button To test whether the indicator light is normal and the relay can operate normal...

Page 9: ...ing time setting value and communication status The LCD backlight is green in normal operation When alarming the residual current reaches the alarming value and the backlight is red When the residual...

Page 10: ...nded The earth fault current is very small and difficult to be estimated operating current can not be reached and the hazardous voltage will appear on the shell TN S system ASJ can be used cut off the...

Page 11: ...and next section only applies to ASJ10L LD1A First Menu Second Menu Third menu Descriptions Addr 1 247 none Address setting bAUd 1200 2400 4800 9600 19200 38400 none Communication Baud rate setting AL...

Page 12: ...turn value of alarm and prewarning operating current is 85 When the leakage current is less than 85 of the rated residual operating current the alarm relay AL1 is reset and when the leakage current is...

Page 13: ...irst event record is generated by the residual current alarm action the alarm value is 200 mA the occurrence time is 11 03 12 08 2 Set the residual current operating value to 50mA _ represents the mod...

Page 14: ...0ms Long press PROG Press Td to modify Press Td to modify number password confirm press PROG Press PROG Press RESET Press Td Press PROG Press RESET Press Td or Td Press PROG Press Td Running PASS Addr...

Page 15: ...Press PROG Press RESET Running PASS XXXX Long press PROG Press Td to modify press Td to modify number password confirm Press PROG Password confirm N Press RESET Addr bAUd AL Td 1 247 Press RESET Pres...

Page 16: ...byte n byte 2 bytes Address code the address code is composed of one byte 8 bit binary at the beginning of the frame and the decimal is 0 255 Only 1 247 is used in the residual current relay and othe...

Page 17: ...ion there is a method to calculate CRC by using the preset table Its main feature is that the calculation speed is fast but the table needs a large storage space This method will not be described here...

Page 18: ...H retain 3 0008H Rated residual operating current setting R W 10 30000mA word 4 0009H Prewarning operating current value R W 10 30000mA word 5 000AH 000FH retain 6 0010H Limit non driving time value R...

Page 19: ...parsing The parameter of address 001CH represents the current setting value as shown in the table below High 8 bit Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Low 8 bit Bit7 Bit6 Bit5 Bit4 Bit3 Bit...

Page 20: ...break line alarm 3 201812 V1 5 Add chapter 4 2 2 4 201912 V1 6 Delete ASJ10L 5 202012 V1 7 Add ASJ10L modify address contact 6 202104 V1 8 Modify AC type output as open Modify some mistake add transf...

Page 21: ...Fax 0086 21 69158303 Web site www acrel electric com E mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industr...

Reviews: