27
communication control
Communication control
self-breaking delay
0~9999s
It is valid when communication control. When set to
0, it is the level control mode. When it is not 0, it is
the pulse control mode. After the delay setting time
is disconnected, the unit is s.
Alarm corresponding to
DO enable
See alarm type description
DI1
Normally open, normally closed
DI initialization state, when the DI state is changed
by the initial state, and the DO is associated with the
alarm, the DO action
DI2
Normally open, normally closed
DI3
Normally open, normally closed
DI4
Normally open, normally closed
Note
:
1. Example: When DO1 selects the output control mode as alarm 1 control or alarm 2 control, and associates A phase
over current alarm and A phase over power alarm, the rest are not associated. When the alarm is generated when the A
phase overcurrent or the A phase over power occurs, the DO1 action occurs.
2. Before selecting the alarm type associated with DO, you need to confirm that the alarm type is checked in the
alarm setting. If it is not checked, DO will not be able to operate when the alarm condition is generated.
6.6 AI Setting
On the main interface, press Menu to enter the menu interface, press
∨
until
“
Parameter Setting
”
is
highlighted, and press
√
to enter the parameter setting interface. Press
∨
until
“
AI Setting Lights up
”
is
displayed, press
√
to enter the AI setting interface. Press
∧
or
∨
to switch the item set by AI, press Enter to
enter the setting of the item, press + or - to change, press > to shift, after the current item setting is changed, press
Exit to exit the item setting. Continue to repeat the above input settings to modify the settings. After the change is
completed, press Exit to enter the password. The default password is 0001 (customer can change the password
according to the password setting set by 7.11 system. If you forget the password, you need to contact us). Press
SaveExit to save the changes and exit, press Esc to exit without saving the changes.
Setting item
range
Description
AI channel
AI01~AI32
Analog input channel selection
Type
None
、
4-20mA
、
0-20mA
、
1-5V
、
0-5V
、
0-10V
Analog input type