ADL200 – User Manual
GENERAL
This 80A direct connect DIN Rail meter is for use with single
phase supplies and measures electrical parameters including
Current (I), Voltage (V), Power (kW/KVA/KVAr), Power Factor
(PF), Frequency (Hz), Imported, Exported and Total Energy
(kWh/kVArh).
It’s MID approved, allowing it to be used for billing applications
and is highly accurate, (Class B, ±1%). With both a Pulse Output
and RS485 Modbus RTU it can be integrated with BMS or
remote monitoring systems.
SPECIFICATION
Meter Type
Single Phase
Fitting Type
DIN Rail
Max. Current (Amps)
80A
MID Approved
Yes
Smart (GPRS modem)
No
Input Type
Direct Connect
Tariffs
Single
Import / Export
Import & Export
Module Width
2
Reference Voltage
AC 220V
Consumption
<4VA
Frequency
50Hz
Accuracy – Active Energy
Class 1
Clock
≤0.5 s/d
Pulse Output
Active Energy
Width of Pulse
80±20ms
Pulse Constant
1000imp/kWh
Interface and
Communication Protocol
Modbus RTU over RS485
Range of Modbus Addresses
1 - 254
Baud Rate
1200bps - 19200bps
Working Temperature
-25
℃
- +55
℃
Relative Humidity
≤95% (No condensation)
IP Rating
IP20
LCD Display
8 digit LCD backlit display
Key Programming
3 keys to view and set
parameters
MEASURED PARAMETERS
Active Energy (kWh)
Active Power (W)
Apparent Energy (kVAh)
Apparent Power (VA)
Current (I)
Frequency (Hz)
Power Factor (PF)
Reactive Energy (kVArh)
Reactive Power (VAr)
Voltage (V)
SETUP
Press and hold the
to enter the setup menu. Enter
the password, (default is “0001”), using the
button to move the cursor and the
button to
change the value, then press
.
Use the
and
buttons to scroll through the
values and press
to amend any settings.
Once complete, press and hold the
button and
select ‘Yes’ to save or ‘No’ to exit without saving
changes.
Symbol
Description
Range
Addr
Modbus Address
1 - 254
bAUd
Baud Rate
1200
,
2400
,
4800
,
9600
,
19200
Pari
Parity Setting
None, Odd, Even
H
High
645 Comms protocol (N/A)
L
Low
645 Comms protocol (N/A)
Led
Backlight Time
0-255 minutes
,
>250 lights to not turn off
S-ty
App. Power Calc.
P Q or U I (N/A)
EF-E
Tariff Set
N/A on this model
dir
Direction of
current
no-Forward, yes-Reverse
COdE
Code settings
1 - 9999
WIRING & INSTALLATION
The ADL200 is designed to be installed on a 35mm DIN Rail
Note: Terminal screw torque – 4.0Nm max