background image

8

 CAUTION:

Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause 

improper and dangerous operation. Verify proper 

operation after servicing.

•  Units are shipped from the factory wired for 240 volt transformer 

operation. For 208V operation, remove the lead from the 

transformer terminal marked 240V and connect it to the 

terminal marked 208V.

•  Optional equipment requiring connection to the power or 

control circuits must be wired in strict accordance of the NEC 

(ANSI/NFPA 70), applicable local codes, and the instructions 

provided with the equipment.

Overcurrent Protection

Overcurrent protection must be provided at the branch circuit 

distribution panel and sized as shown on the unit rating label and 

according to applicable local codes. Generally, the best fuse or 

breaker for any heat pump is the smallest size that will permit 

the equipment to run under normal usage and provide maximum 

equipment protection. Properly sized fuses and breakers also 

prevent nuisance trips during unit startup

NOTE: If a fuse blows or a breaker trips, always determine 

the reason. Do not arbitrarily install a larger fuse or breaker 

and do not, in any case, exceed the maximum size listed 

on the data label of the unit.

Grounding

 WARNING:

The unit cabinet must have an uninterrupted or 

unbroken electrical ground to minimize personal 

injury if an electrical fault should occur. Do not 

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with 

local codes or, in the absence of local codes, with the National 

Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical 

Code. Use the grounding lug provided in the control box for 

grounding the unit.

Thermostat / Low Voltage Connections

•  The unit is designed to operate from a 24 VAC Class II control 

circuit. The control circuit wiring must comply with the current 

provisions of the NEC (ANSI/NFPA 70) and with applicable 

local codes having jurisdiction. Thermostat connections should 

be made in accordance with the instructions supplied with the 

thermostat and the indoor equipment.

•  A heat pump thermostat is equipped with a system HEAT-

COOL EM HEATswitch, which provides a positive means of 

preventing simultaneous operation of the heating and cooling 

units. The thermostat is also equipped with an ON-AUTO fan 

switch which allows the home owner to operate the indoor 

blower when air circulation is desired.

•  Connect the low voltage wires to the respective terminals 

on the thermostat base. See 

Figure 13 (page 21)

 and 

the thermostat instruction sheet for more detailed wiring 

information.

•  The thermostat should be mounted about 5 feet above the 

floor on an inside wall. DO NOT install the thermostat on an 

outside wall or any other location where its operation may be 

adversely affected by radiant heat from fireplaces, sunlight, or 

lighting fixtures, and convective heat from warm air registers or 

electrical appliances. Refer to the thermostat manufacturer’s 

instruction sheet for detailed mounting information.

Defrost Control Board Test Pins

•  Placing a jumper between the test pins for less than 1 second 

will bypass the Anti-Short Cycle Timer.

•  Placing a jumper between the test pins for more than 1 second 

will force the unit into a defrost cycle. As soon as the jumper 

is removed, the defrost cycle will end as determined by the 

typical criteria.

•  To determine operating status or fault conditions, refer to 

Table 2 (page 10)

 for diagnostic description.

Clearing Defrost Board Fault Codes

• Fault codes can be removed from memory through the use of 

the test pins. This is accomplished by shorting the two test 

pins momentarily (more than 1 second) while there is no Y1 

IN input present.

• Without resetting using the test pins, the fault codes will stay 

in the board’s memory continuously (even through loss of 

power) for 7 days.

Electric Heat Package (optional)

This heat pump is shipped without an auxiliary electric heat kit 

installed. If electric heat is desired, an accessory heater kit must 

be field installed. Refer to 

Table 1 (page 9)

 for blower speeds.

•  Select the correct size heat package for the installation. See 

specifications sheet for available kits and application. Install 

the heater kit according to the to the installation instructions 

provided with the kit.

•  Installation is most easily accomplished before making duct 

or electrical connections.

Outdoor Thermostat Options

HUD Outdoor Thermostat Option

This thermostat prevents the operation of supplemental electrical 

resistance heat at outdoor temperatures above 40° F, except for 

defrost operation. For additional info refer to Title 24: Housing and 

Urban Development-Subpart H, Section 3280.714, Paragraph 

1, Item ii.
1. Remove the white wire between terminal W2 (on the terminal 

strip) and W2 IN terminal (on the defrost board) and discard. 

See 

Figure 13 (page 21)

 for additional wiring connections.

2. Move the white jumper wire from W2 terminal (between E 

and W2 on the terminal strip) and connect to W2 IN terminal 

(on the defrost board).

2nd Stage Thermostat Option

Models without an outdoor thermostat have a white wire from 

W2 on the terminal strip to W2 on the defrost board for the use 

of supplemental electrical resistance heat for a W2 or E call. For 

2nd stage outdoor thermostat wiring connections, see 

Figure 13

.

A jumper wire is supplied from W2 to E on the terminal strip 

on all models.

Blower Speed

For optimum system performance and comfort, it may be 

necessary to change the factory speed setting. See 

Table 1

 

for factory settings.

 WARNING:

To avoid electric shock, personal injury, or death, 

turn off the electric power at the disconnect or the 

main service panel before making any electrical 

connections.

Summary of Contents for Q7RE Series

Page 1: ...mportant role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result...

Page 2: ...Air Circulation 10 System Heating 10 System Cooling 10 Short Cycle Protection 10 Emergency Heat 10 Forced Defrost Mode Field Test 10 Anti Short Cycle Timer Test 11 Heating Mode 11 Cooling Mode 11 COMP...

Page 3: ...d any other flammable vapors and liquids in the vicinity of the unit CAUTION This unit uses R 410A refrigerant DO NOT use any other refrigerant in this unit Use of another refrigerant will damage the...

Page 4: ...rating plate for the proper circulating air flow and temperature rise It is important that the duct system be designed to provide the correct flow rates and external pressure rise An improperly desig...

Page 5: ...insulated to minimize duct losses and prevent condensation Use insulation with an outer vapor barrier Refer to local codes for insulation material requirements HEAT PUMP INSTALLATION Unpacking the Uni...

Page 6: ...or joists Care should be taken when cutting throughcarpetingtoavoidsnags NOTE Inmostinstallationsit will be necessary to cut a similar hole in the fiberboard directly under the hole in the floor Howev...

Page 7: ...rical box of the unit The installer should become familiar with the wiring diagram before making any electrical connections to the unit An electrical disconnect must be located within sight of and rea...

Page 8: ...her location where its operation may be adversely affected by radiant heat from fireplaces sunlight or lightingfixtures andconvectiveheatfromwarmairregistersor electrical appliances Refer to the therm...

Page 9: ...28 1084 29 1027 31 967 33 Tap T3 1266 25 1332 24 1291 24 1245 25 1192 27 1132 28 1067 30 995 32 Tap T4 1518 21 1481 21 1442 22 1400 23 1355 23 1307 24 1256 25 1202 26 Tap T5 1686 19 1644 19 1601 20 15...

Page 10: ...ting Set the thermostat system mode to HEAT and the fan mode to AUTO Change the thermostat temperature selector above the existing room temperature and check for the discharge of warm air at the suppl...

Page 11: ...to the System Heating section on page 10 Anti Short Cycle Timer Test The 5 minute time delay feature can be bypassed by shorting the TEST pins together Heating Mode WhentheTESTpinsareshortedtogetherfo...

Page 12: ...75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 238 135 137 239 139...

Page 13: ...R TEMPERATURE F 70 75 80 85 90 95 100 105 LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP LIQ PRESS DIS TEMP 135 26...

Page 14: ...e suction pressure will vary from design value if outdoor air flow entering dry bulb or entering wet bulb temperatures vary NOTES 1 All pressures are listed psig and all temperatures in F 2 Discharge...

Page 15: ...63 124 69 283 130 84 307 145 105 352 166 126 396 188 43 231 109 52 249 116 61 268 122 70 287 128 85 314 142 106 359 162 127 403 182 44 238 107 53 255 114 62 273 120 71 290 126 86 321 139 107 366 157 1...

Page 16: ...115 47 242 123 58 268 132 69 294 141 84 324 158 104 374 183 124 424 208 38 223 113 48 248 121 59 273 130 70 298 139 85 331 155 105 381 178 125 431 201 39 230 111 49 254 119 60 278 128 71 301 137 86 3...

Page 17: ...ctric Heater Power Supply 1 125 Power Supply 0 875 Low Voltage Supply Control Access Panel Blower Access Panel H 17 86 15 36 10 10 3 4 NPT Drain Connection 1 12 13 1 38 3 2 3 2 5 29 Side View MODEL NU...

Page 18: ...connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant de faire letretine 2 Emp...

Page 19: ...servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105 C 1 Couper le courant avant...

Page 20: ...1 Disconnect all power before servicing 2 For supply connections use copper conductors only 3 Not suitable on systems that exceed 150V to ground 4 For replacement wires use conductors suitable for 105...

Page 21: ...nd stage outdoor thermostat is field supplied NOTE 2 HUD outdoor thermostat is not factory installed in all models For HUD applications Remove white wire between terminal W2 and W2 IN terminal C G O W...

Page 22: ...22...

Page 23: ...23...

Page 24: ...essure high side Stage 1 Suction Pressure low side FILTER SYSTEM Filter s secured in place YES NO Filter s clean YES NO 10331420 Replaces 10270500 INSTALLER PLEASE LEAVE THESE INSTRUCTIONS WITH THE OW...

Reviews: