User manual
35
ACOWA INSTRUMENTS, Industrivej 10, 8305 Samsø - VAT-no: 36562919 – mail: [email protected] – Phone: +45 7221 7979
Register list ”quick-guide”
In- and output.
Analog input
Signal type
UINT32
INT32
INT32
INT32
INT32
INT32
INT32
Status/Alarm
Actual value
Max.
yesterday
High limit
High alarm
limit
Low limit
Low alarm
limit
AI 1
0/4-20mA
Høj grænse 8:0
Lav grænse 8:2
20
192
22
2011
24
2019
Digital input
Signal type
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
Status/Alarm
pulse total
pulses today
pulses
yesterday
Operating time
total (secs.)
Operating
time today
(secs.)
Operating time
yesterday
(secs.)
DI 1
”low” < 5V.
”high” > 12V.
4:0
500
600
700
550
650
750
DI 2
”low” < 5V.
”high” > 12V.
4:1
502
602
702
552
652
752
Description
(Seconds)
(Seconds)
(Seconds)
Digital output
Signal type
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
Status/Alarm
pulse total
pulses today
pulses
yesterday
Operating time
total (secs.)
Operating time
today (secs.)
Operating time
yesterday
(secs.)
DO 1
Relay max 2A
2:3
804
904
1004
854
954
1054
DO 2
Relay max 2A
2:4
806
906
1006
856
956
1056
Description
(Seconds)
(Seconds)
(Seconds)
Pump
Signal type
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
UINT32
Status/Command
Starts
total
Starts
today
Starts
yesterday
Operating time
total (secs.)
Operating time
today (secs.)
Operating time
yesterday (secs.)
Pump
Reley max 12A
(Pump)
70
100
128
156
108
136
164
Description
See section “pump
word list”
(Seconds)
(Seconds)
(Seconds)
Pump control.
Time and date
UINT32
System
information
UINT32
System
information
UINT16
System
information
STR20/32
Seconds
80
Id number
0
TCP-port
2566
Name
2844
Minuttes
82
GSM-signal
94
GPRS-timeout
2564
Municipal
2854
Hours
84
IP-Address
2564
Geographical
location
2870
Day
86
APN
2548
Month
88
Year
90
Summary of Contents for PUMA