background image

 

30309218                                                                                                                                                          Issue 1.13

 

 

Providing 2 tones. 

 

Standard: EN 54-3. 

Description 

C-9403  Conventional  Sounder  Strobe  is  an  audible 
and visible  alarm  device  used to  warn  people in  field 
when fire occurs. It can give audible and visible alarm 
signal  when  applied  to  external  24VDC  power  (D1 
connected with positive and D2 with negative). 
A 25.5mm high shallow base and a 40mm high deep 
base  are  available.  Unless  otherwise  stated,  all 
descriptions  in  this  manual  take  the  shallow  base  as 
example. 

Connection & Cabling 

Terminals on the base are shown in Fig. 2. 
 

?

110

110.4mm

95.9mm

S

hal

low

 Base

De

ep 

Base

Tamper-proof
knockout

Drain Hole

Fig.1

1

D

2

K

1

2

Z

K

Z

1

S

2

D

mm

G

Arrow Upward

Fig. 2

 

 

G(10),  D1(9),  D2(7):  Connecting  with  24VDC  power, 
polarity-sensitive. G connects with positive output, D1 
with 

positive 

input 

and 

D2 

with 

negative. 

Recommended Wiring 

1.5mm

2

  or  above  fire  cable  for  24VDC  power  line, 

subject to local codes. 

Installation 

 

When surface mounted, the sounder strobe should 
be  placed  0.2m from the  ceiling for normal  space 
height.  When  the  conduit  is  embedded,  the  base 
can  be  mounted  on  the  back  box.  When  the 
conduit is surface mounted, the deep base should 
be adopted. Knock the knockout hole, and connect 
the conduit with it. The mounting hole spacing and 
mounting  direction  are  shown  in  Fig.  2.  Mounting 
method is shown in Fig. 3a and Fig. 4. The conduit 
must be embedded when the shallow base is used, 
as shown in Fig. 3b. 

 

The  base  and  the  sounder  strobe  are  twisted 

together.  When  mounting,  remove  the  sounder 

strobe, thread cables through the cable entry in the 

base  and  connect  with  corresponding  terminals, 

then twist the sounder strobe onto the base. 

 

 

 

                                                                                                                       

 

 

 

 

 

 

 

Fig. 3a 

Conduit

Back Box

Sounder Strobe

 

Fig. 3b 

Sounder Strobe

Conduit

 

Fig. 4 

 

If the sounder strobe is required to be tamper-proof, 
knock down the arch knockout as shown in Fig.  1 
and  fix  it  with  ST2.9×6.5  self-  tapping  screws  (in 
this  case,  it  can  only  be  removed  by  a  cross 
screwdriver). 

Application 

Tone can set through pins inserted on the main circuit 
board.   

C-9403 

  Conventional Sounder Strobe

 

548e/01 

2831-CPR-F0128 

GST-0003-01 

 

13 

www.acornfiresecurity.com

www.acornfiresecurity.com