Regular testing, inspection and maintenance
87/ 100
Oleolift-C
5.2 Half-yearly maintenance
of the light liquid separator
IMPORTANT
■
Biannual maintenance and inspection (after prior emptying and cleaning) is only
permitted by qualified, competent people,
Chapter 1.5 "Personnel qualifications"
(applies only to Germany. Provisions in other countries can vary).
■
If defects are identified during the tests or inspections, then the light liquid separator
plant must not be put back into service until these defects have been remedied.
Inspections executed, maintenance and test results, any defects and their remedial works must
be documented in the operating log.
Scope of the maintenance work, Chapter 4.7 "Self-monitoring of the light liquid separator".
In addition to the self-monitoring measures, the following work must also be done:
■
Control the coalescence insert for damage and exchange it when required;
■
Check on the visible interior areas and installed parts and coatings by means of visual
inspection for recognisable damage and for anything unusual e. g. raised water level,
discolouring, bubble formation, delamination, corrosion etc;
■
The sensors of the warning system type idOil 30 are cleaned and checked when
triggered in accordance with the manufacturer's instructions,
assembly and
operating instructions "idOil -30 - Labkotec";
■
Empty and clean the separator chamber in the event of exceptional contamination;
■
Cleaning the sampling device.
IMPORTANT
It should be additionally noted that even components which are not directly part
of the separator plant must also be serviced and maintained regularly, otherwise the proper
operation of the separator plant cannot be ensured.