Installation
47/ 100
Oleolift-C
3.4.5 Mount idOil sensors
IMPORTANT
■
To facilitate easy removal of the sensors for cleaning or testing, it is recommended that
the sensor cables be sufficiently long and coiled up and fixed in the cover plate. With
the build-up sensor (fixed to the holder of the coalescence insert) the complete removal
of the coalescence insert with accumulation probe must be guaranteed.
■
Oil layer sensors idOil-OIL / 1 + 2 must be suspended in a freely movable manner in the
separator chamber after installation
■
Electrical connection in the cable connector,
Section 3.5.8 "Connecting the LCJ1-3
cable connector"
idOil sensors (idOil-LIQ high liquid level sensor and 2 idOil-OIL oil layer sensors, each with 5 m
connection cable), 1 LCJ3 cable connector and 3 sensor mounting kits (dowels, screw hooks
and cable ties) are supplied loose on delivery.
The cable connector (protection type IP 68) is resistant to mineral oil and is suitable for use in
ATEX Zone 0.
5 m
Maximum 1,000 m
1
2
3
4
5
6
7
8
1 = idOil-LIQ high liquid level sensor
2 = idOil-OIL / 1 oil level sensor
3 = idOil-OIL / 2 oil level sensor
4 = Connection cable / (each 5 m long) for the sensors
5 = LCJ3 cable connector
6 = Cable gland
7 = On-site extension cable
8 = idOil warning device (built into the control unit)
Position of the idOil sensors
IMPORTANT
■
The two idOil-OIL /1 + 2 oil layer sensors
are to be fixed in the maintenance
opening above the separator chamber,
position .
■
The screw hook for the cable of the
idOil-LIQ high liquid level sensor is to
be fixed above the separator chamber,
position .