Product Description
17/ 100
Oleolift-C
2.1.4 Oleolift control unit
■
Functional and safety-relevant for Oleolift-C in combination with submerged pump
■
Operating voltage: 400 V– frequency: 50 Hz
■
Degree of protection: IP 52
■
Selection or version according to motor protection switch:
2x 2.5 - 4 A
2x 4 - 6 A
2x 6 - 10 A
2.2 Accessories
Component
Version
Weight
Pump drive chain
■
Pump drive chain incl. shackle
■
Made of stainless steel
■
Load-bearing capacity 200 kg
■
Length 4 m
15.5 kg
Rechargeable
battery
■
To maintain alarm signal in the event of a power failure
■
12 V/1.2 aH
0.8 kg
Outdoor cabinet
■
As empty housing
■
Dimension: 806 x 2,000 x 338 mm (Wx H x D)
■
With horizontal partition wall
■
Area above the partition:
■
Spare space for a local Multi-Control mono or duo switching
device, with socket 230 V and 400 V
■
Area below the partition wall: Space reserved for a local backflow
loop DN 50 - 200, with 100 W heater with thermostat
40 kg
Protective pipe
■
Protective tube for level sensor
■
Length 1,220 mm
1 kg
Ex-safety-barrier
In combination with level sensor
■
For separating potentially explosive and safe area. The ex-safety-
barrier is an additional piece of equipment whose purpose is to
achieve safe isolation of intrinsically safe electric circuits from
non-intrinsically safe electric circuits. It contains limiting devices
with voltage limitation for two circuits.
■
Maximum permissible ambient temperature: -20 °C to +50 °C