ACME FAN-JET Installation Instructions Download Page 1

ACME ENGINEERING &

MANUFACTURING CORP.

P.O. Box 978

Muskogee, Oklahoma 74402

918/682-7791 FAX: 918/682-0134

FORM 610008

INSTALLATION INSTRUCTIONS

FAN-JET

®

HEATING ACCESSORY

CAUTION! Acme Ventilation Systems are designed to

operate under negative pressure with timers and ther-

mostats. Only heaters designed to operate within these

specific conditions should be utilized with an Acme

Ventilation System.

FAN-JET MODEL

HP

TUBE SIZE

CFM

MOTORIZED SHUTTER

MODEL

FRAMED OPENING

* HEATING CAPACITY WITH HEAT-KIT

BTU/HR. OUTPUT HEATER TEMP RISE OF:

DISTANCE FROM

HEATER TO

FAN-JET

®

OPENING*

IN

MM

IN

MM

40

50

60

70

IN

MM

RC18E6

14

18

457

3120

WAAC2626MT

23 X 23

584 X 584

112,000

138,000 163,000 186,000 30 - 48 762 - 1219

RC24F/RCA24F

1

3

24

610

5420

WAAC3333MT

30 X 30

762 X 762

172,000

212,000 250,000 287,000 30 - 60 762 - 1524

RC30G/RCA30G

1

2

30

762

8550

WAAC4040MT

37 X 37

940 X 940

278,000

342,000 403,000 463,000 30 - 60 762 - 1524

RC30J/RCA30J

1

30

762 10600

WAAC4040MT

37 X 37

940 X 940

345,000

424,000 500,000 574,000 30 - 60 762 - 1524

The unit heater louvers should be at the same elevation as the

Fan-Jet inlet opening and spaced a proper distance from it, with the

axis of the unit heater discharge opening directed toward the

Fan-Jet inlet opening. If this is not done, flame disturbance can

result which can lead to flame impingement on the heat exchanger

and eventually heat exchanger failure. It can also cause pilot

outage problems leading to nuisance service calls or loss of heat in

the structure.
If the Fan-Jet end of the structure is colder than the remainder of the

structure, correct by adjusting one or two of the lower louvers of the

heater to a downward position to divert part of the heated air to the

end wall area.

CAUTION:

Avoid combustion malfunctions when two heaters are

used with one Fan-Jet. The minimum heater from Fan-Jet opening

distance must be maintained. Both heaters must operate

simultaneously, unless center baffle is used and the discharge

louvers must be directed toward the top of the Fan-Jet opening.

CAUTION!

These units have rotating parts and safety precautions

should be exercised during installation, operation and

maintenance.

Notice.

In cases where motor with capacitor is used, the motor

base screws must be loosened and the motor housing rotated such

that the capacitor is approximately 45 degrees above the horizontal

position when viewing the shaft end of the motor as shown in Figure

1 on Page 2.

1. These instructions are intended to be used in conjunction with

the installation instructions for the Fan-Jet convection tube

system which comes attached to the Fan-Jet unit. Follow the

location and framing in the Fan-Jet instructions and the

installation instructions that come with the unit heater.

2. The horizontal struts shipped with the Fan-Jet will not be used

with the heating accessory. The proper spacing of the Fan-Jet

unit will be accomplished with the heat intake top and bottom

pieces and the diagonal extended struts shipped with the

Fan-Jet.

3. The heat shield should be assembled to the Fan-Jet unit using

the appropriate exploded view (shown on page 2) as a guide.

4. The Fan-Jet unit should now be supported as indicated in items

8 and 9 of the Fan-Jet instructions, Form 610001.

5. Attach the heat shield assembly to the framed opening with the

fasteners provided.

6. Continue with the installation of the tubing as directed in items

12 through 32 of the Fan-Jet Installation Instructions 610001.
The center baffle must be installed whenever two unit heaters

are used with a Fan-Jet unit and are staged to operate at

separate times. The baffle will prevent “blow thru” from one unit

heater to the second that may result in reverse rotation of the

second heater fan or may affect the pilot light of the second

heater.

FAN-JET PERFORMANCE DATA

Framed opening furnished by others.

* The output BTU rating of gas fired heaters is 80% of their input BTU rating.

See CAUTION*