RD2402D SERIES

Installation & Operation Instructions

Phone:

 1-888-967-5224

Website:

 workaci.com

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE 
MAY BE AFFECTED.

GENERAL INFORMATION

The RD2402D is an output module that works with the MOD9200 series network transceivers to output two (2) 
wireless digital signals (dry contact) for wireless control of modulating actuators or wireless status indications.  The 
network transceiver receives the wireless signal from the sensor/input concentrator and that data is sent to the 
BAS via RS-485.  If the BAS determines an action is needed, it then sends the command to the transceiver and the 
transceiver sends that command wirelessly to the RD2402D, which then outputs a digital signal. 

The maximum radio transmission distance is dependent on the building type. In a typical commercial 
building with steel I-Beam construction, concrete floors with reinforcing rod, and metal stud walls, it can be 
expected that transmissions will penetrate horizontally approximately 200-300 feet of floor, walls, furniture 
and air.

Generally, a wireless system will cover at least three floors–one floor above, and one floor below the receiver 
location. In some buildings with favorable transmission characteristics the system may cover more floors - 
see 

FIGURE 2, 

p.2. Wireless sensor transmitters should be installed within 200 to 300 feet of the RM2432D 

receiver.

RR2552 signal repeaters can be installed as needed to increase transmission distance between sensors and 
receivers - see 

FIGURE 1

PRECAUTIONS
• To maintain high performance, do not install sensors, repeaters, or receivers in the following areas: 

- Inside metal enclosure / panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or large body of water
- Do not mount above false ceiling. Mount in wall 1” below ceiling. 

MOUNTING INSTRUCTIONS

Mount the RD2402D as close to the equipment or 
controller as possible using four #8 screws 
(mounting dimensions see 

Figure 3

). 

WIRING INSTRUCTIONS

WIRING PRECAUTIONS
• Do NOT run Analog/Digital Output wires 

in any conduit with line voltage 
(24/120/230 VAC).

• Remove power before wiring. NEVER 

connect or disconnect wiring with power 
applied.

• The RD2402D is full wave rectified.
• It is recommended that you use an 

isolated UL-listed Class 2 transformer 
when powering the unit with 24 VAC. 
Failure to wire the devices with the 
correct polarity when sharing transform-
ers may result in damage to any device 
powered by the shared transformer.

Observe polarity when connecting analog 
outputs to the controller inputs.

Connect 24VAC 60Hz to the TB1 terminals using 
16-26 twisted pair wire. Check all connections 
before applying power to the unit.

Connect the digital outputs to the appropriate control input terminals on the controller using 16-26 AWG 
wire. Each output needs 2 wires. Do not Jumper Commons for relay outputs.
 

FIGURE 1: 

WIRELESS BUILDING DIAGRAM

SENSOR

REPEATER

RECEIVER

REPEATER & RECEIVER

1’ FROM CEILING

Summary of Contents for RD2402D Series

Page 1: ...e building type In a typical commercial building with steel I Beam construction concrete floors with reinforcing rod and metal stud walls it can be expected that transmissions will penetrate horizontally approximately 200 300 feet of floor walls furniture and air Generally a wireless system will cover at least three floors one floor above and one floor below the receiver location In some buildings...

Page 2: ...ctified It is recommended that you use an isolated UL listed Class 2 transformer when powering the unit with 24 VAC Failure to wire the devices with the correct polarity when sharing transform ers may result in damage to any device powered by the shared transformer Observe polarity when connecting analog outputs to the controller inputs Connect 24VAC 60Hz to theTB1 terminals using 16 26 twisted pa...

Page 3: ... 5224 Website workaci com Page 3 Version 6 0 I0000690 6 73 171mm 4 76 121mm 6 26 159mm 3 58 91mm 6 73 171mm Ø0 18 Mounting Holes 2 17 55 1mm TOP VIEW SIDE VIEW TOP 24VAC 6 75 171 5mm 3 5 88 9mm Ø0 190 4 PLCS 7 285 185mm 6 12 155 5mm 4 72 119 89mm 2 367 60 12mm TOP TOP VIEW SIDE VIEW Antenna Active LED Data Link LED 24VAC ...

Page 4: ...tally depending on building type and constructions and typically one floorabove and below the transceiver vertically Two 2 SPDT Pilot Duty Relays Dry Contact 1 0A 30 VDC 104ºF 40ºC 0 5A 125 VAC 104ºF 40ºC Resistive Mechanical 5 000 000 operations minimum 36K operations hr Electrical 100 000 operations minimum under rated load 1 8K operations hr 1 SPDT Dry contact relay 1 0A 30 VDC 104ºF 40ºC 0 5A ...

Reviews: