Installation and Operation Instructions 

EPC 

 

Analog Current or Voltage Input to Modulated Pressure Output 

With Bleed Orifice 

 

INSTALLATION 

READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION. 

 

Ground yourself before touching board.  Some components are static sensitive. 

Mounting: 

Circuit board may be mounted in any position.  If circuit board slides out of snap track, a non-conductive 
“stop” may be required.  Use only fingers to remove board from snap track.  Slide out of snap track or push 
against side of snap track and lift that side of the circuit board to remove.  Do not flex board or use tools.

 

 

POWER CONNECTIONS – THIS PRODUCT ACCEPTS 24 VDC OR 24 VAC POWER

Be sure to follow all local electrical codes.  Refer to wiring diagram for connection information.  

Be sure to make all connections with the power off

1.)  DC Power – Refer to wiring diagram for connection information. 

          If the 24 VDC power is shared with devices that have coils such as relays, 
          solenoids, or other inductors, each coil must have an MOV, DC Transorb, or diode 
          placed across the coil or inductor.  The cathode, or banded side of the DC Transorb 
          or diode, connects to the positive side of the power supply. 

                  2.)  AC Power – Refer to wiring diagram for connection information. 

                                      Check the wiring configuration of any other loads that may be connected to this   
                                      transformer.  If required by BAS or controller specification, the 24 VAC neutral can 
                                      be

 

earth grounded at the transformer.  Analog input, digital input, and analog output 

                                      circuits should not be earth

 

grounded at

 

two points.  Any field device connected to                 

                                      this transformer must use the same common.  If you are not sure of other field 
                                      device configuration, use separate transformers for isolation. 
 

 

         If the 24 VAC power is share with devices that have coils such as relays, solenoids,  

                                      or other inductors, each coil must have an MOV, AC Transorb, or other spike  
                                      snubbing device across each of the shared coils.  Without these snubbers, coils  
                                      produce very large voltage spikes when de-energizing that can cause malfunction or  

NOTE
    #1

Power

(+)

(-)

Analog Input Signal

(+)

(-)

Branch Pressure
Feedback Signal

Override Feedback
(Dry Contact)

Manual Override Pot
and Manual/Auto

Switch

Offset Pot - Set for minimum desired

pressure with minimum input signal

Span Pot - Set for maximum desired

pressure with maximum input signal

Zero Pot is Factory Set - Do not adjust

SEE

 NOTE
    #1

(+)

A

B
C

J2

0-10 psi

A

B
C

J2

0-15 psi

A

B

C

J2

0-20 psi

10V

15V

J1

5V

20mA

0-5 VDC

10V
15V

J1

5V

20mA

0-10 VDC

10V

15V

J1

5V

20mA

0-15 VDC

10V
15V

J1

5V

20mA

0-20mA

Pressure Output Range Selector

Signal Input Range Selector