GENERAL INFORMATION

The DT2630 is a battery operated wireless duct sensor 
that gives the flexibility and ease of installation for 
monitoring duct temperatures wirelessly using 
900MHz spread spectrum technology rather than 
costly hardwire installations.  The single point probe is 
0.25” O.D., made of 304 stainless steel, and is available 
in 4”, 6”, 8”, 12”, and 18” lengths to fit most applications.  
The DT2630 can be ordered with the standard 
enclosure or NEMA 4X enclosure depending on the 
specifications required. The DT2630 will send the 
temperature wirelessly to the RM2432D receiver that 
converts the wireless signal to voltage input for use 
with a DDC controller, or to a transceiver which will 
send the data to a BAS using BACnet, Modbus, or 
Lonworks protocol.  Transmission distance in a typical 
building is 200-300 feet horizontal depending on the 
layout and construction of the building, and one floor 
above and one floor below the transceiver. Sensor 
distance and reliability can be increased with the 
addition of a RR2552B(s) repeater.

For optimal temperature readings, follow these 
tips:  

Duct probe should be placed (3) to (4) duct 

segments down from any bend or obstructions and 
away from 90° bends. 

Mount the sensor on the top or sides of duct 

work; mounting on the bottom risks damage 
due to moisture.

The sensor should be mounted in the middle of the 

duct where air circulation is well mixed (no 
stratification), and not blocked by obstructions. 
Stratification and obstructions can cause sensing 
errors. An example is downstream from a heating 
or cooling coil.

MOUNTING INSTRUCTIONS

Drill a 7/8” hole in the duct and insert the probe 
through the hole until the foam pad is tight to the 
duct. Drill pilot holes for the mounting screws. Use the 
enclosure flange as a guide, or use the dimensions 
listed below to measure out. 

FIGURE 1: 

DIMENSIONS

DUCT TEMPERATURE SERIES

Installation & Operation Instructions

DT2630

Phone:

 1-888-967-5224

Website:

 workaci.com

1.88"

(47.752 mm)

2.25"

3.20"

(81.28 mm)

5.25" (133.35 mm)

5.78" (146.812 mm)

Ø 0.19"

Battery Positive 

Terminal

Internal Link Button

1/2" NPSM

Process Thread
304 Stainless Steel

0.25" Probe

DT2630A-0x

2.56"

(65.024 mm)

4.53" (115.062mm)

2.23"

(56.642 mm)

Battery Positive 

Terminal

Internal Link 

Button

1/2" NPSM

Process Thread

304 Stainless Steel

0.25" Probe

DT2630AE-0x

STANDARD

NEMA 4X

Now fasten and insert (2) screws #8 x 3/4" TEK 
(provided and recommended) through the 
mounting holes in the flange and tighten until the 
unit is held firmly to the duct. 

Note:

 Wireless sensors should be installed within 200 

to 300 feet of the receiver.  RR2552 signal repeaters can 
be installed as to increase transmission distance 
between sensors and receivers.

To select the proper sensor location, first install and 
power the receiver.  To activate the sensor insert the 
battery observing the polarity. The mesh networked 
wireless system does not require any additional 
wireless equipment to determine the proper location of the sensors.

While the sensor is attempting to connect to the receiver the Data-Link LED will blink rapidly 8–10 times 
every 10 seconds. Once a connection has been established the Data-Link LED will blink once to indicate the 
data transmission has been received successfully. The Data-Link LED will continue to blink once for every 
data transmission. The data transmission rate is programmed into the sensor (normally 1 minute intervals).  

If the sensor continues to blink rapidly 8-10 times every 10 seconds, a repeater will need to be added. See 
RR2552B instructions for repeater installation.

The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A low 
battery signal is also sent to the receiver for remote indication that the battery should be replaced. If the 
battery is not replaced in approximately 2 months the battery voltage will become so low that the Low 
Battery and Data-Link LEDs will not blink. Replace the battery and the Data-Link LED will start blinking 
while the sensor is re-establishing communications with the receiver.

Attach the cover of the duct sensor by installing the four screws to complete the installation.

PRECAUTIONS
SENSORS, REPEATERS AND RECEIVERS SHOULD NOT BE INSTALLED IN THE FOLLOWING AREAS:
• INSIDE METAL ENCLOSURE / PANEL 
• INSIDE OR IMMEDIATELY NEXT TO ELEVATOR SHAFT / ELEVATOR BANKS
• IN FRONT OF OR IMMEDIATELY NEXT TO LARGE TREES OR LARGE BODY OF WATER
TRANSMISSION DISTANCE AND PERFORMANCE WILL BE DRASTICALLY REDUCED.

CAUTION:
DO NOT USE THIS PRODUCT IN ANY SAFETY RELATED APPLICATIONS WHERE HUMAN LIFE 
MAY BE AFFECTED.