![aci DMUX-8S Installation & Operation Instructions Download Page 1](http://html.mh-extra.com/html/aci/dmux-8s/dmux-8s_installation-and-operation-instructions_457935001.webp)
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone:
1-888-967-5224 |
Website:
workaci.com
Page 1
Version: 4.0
I0000594
GENERAL INFORMATION
The DMUX-8S is a selectable output controller
designed to expand the output capacity of an
energy management or process controller. The
DMUX-8S has up to eight output relays. Common
(C), Normally Open (NO), and Normally Closed (NC)
connections are available for each output. Three
position On/Off/Auto jumpers are standard and
allow manual override at the DMUX-8S. It converts a
relay, transistor or Triac input signal to operate an
appropriate relay output based on the duration of
the signal. The relay output has an LED indicator for
a visual verification of operation. There are also LED
indicators to show the presence of power to the
DMUX-8S and the input pulse. This program offers
different modes of operation using the Solidyne™
fast pulse input. This device is DIP switch selectable
for sequencing, or Rooftop Unit 8 relay control or
Rooftop Unit 5 relay control.
MOUNTING INSTRUCTIONS
The circuit board may be mounted in any position. If the circuit board slides out of snap track, a
non-conductive “stop” may be required. Use only fingers to remove board from snap track. Slide out of
snap track or push up against side of snap track and lift that side of the circuit board to remove.
Do not flex
board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect or disconnect wiring with power applied.
• When using a shielded cable, ground the shield only at the controller end. Grounding both
ends can cause a ground loop.
• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may
result in damage to any device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC
Transorb or diode, connects to the positive side of the power supply. Without these snubbers,
coils produce very large voltage spikes when de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and National Electric Codes.
FIGURE 1:
DIMENSIONS
INTERFACE SERIES
Installation & Operation Instructions
DMUX-8S
Phone:
1-888-967-5224
Website:
workaci.com
3.22"
(81.78mm)
4.82" (122.42mm)
L10
J10
J9
L9
J1
J4
J2
J3
L2
D2
K2
L1
D1
K1
L4
D4
K4
L3
D3
K3
= AUTO
A
= OFF
-
= ON
O
PULSE
TRIAC NORM
PWR
+
AC
-
DC
IN
+
-
M 1
POWER
D
E
3
O 2
C2
NC
NO
C1
NO
NC
A
O
A
O
NO
NC
C4
C3
NC
NO
A
O
A
O
3
3.25"
(82.55mm)
4.69" (119.13mm)
0.70”
(17.78mm)
This program offers different modes of operation using the Solidyne™ fast pulse input. Input ranges are
given in percentages from 4-96% and also milliseconds from 10-230ms. Relay action does not occur until
receiving 10 identical cycles of the same range. Any input range that is less than 4%, greater than 96%, or
after 5 seconds with NO input pulse will command an ALL OFF relay action.
Apply power: The “POWER” LED should light. Close the pulse input relay contacts: The “PULSE” LED should
light indicating that the M978 is receiving the PWM signal. Further test the M978 operation by comparing
the operation of output relays with respective input pulse. The LED for each relay will turn on when the
respective relay is activated. No action on longer pulses.
SEQUENTIAL RELAY CONTROL
The program has to see 10 identical pulse cycles before a sequencing relay action can occur.
NOTE:
<4%, >96%, or no pulse = ALL OFF
DIP SWITCH selections: OFF- 1, 3, 4 ON- 2 (only)