aci DMUX-8S Installation & Operation Instructions Download Page 1

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 4.0

I0000594

GENERAL INFORMATION

The DMUX-8S is a selectable output controller 
designed to expand the output capacity of an 
energy management or process controller. The 
DMUX-8S has up to eight output relays. Common 
(C), Normally Open (NO), and Normally Closed (NC) 
connections are available for each output. Three 
position On/Off/Auto jumpers are standard and 
allow manual override at the DMUX-8S. It converts a 
relay, transistor or Triac input signal to operate an 
appropriate relay output based on the duration of 
the signal. The relay output has an LED indicator for 
a visual verification of operation. There are also LED 
indicators to show the presence of power to the 
DMUX-8S and the input pulse. This program offers 
different modes of operation using the Solidyne™ 
fast pulse input.  This device is DIP switch selectable 
for sequencing,  or Rooftop Unit 8 relay control or 
Rooftop Unit 5 relay control.

MOUNTING INSTRUCTIONS

The circuit board may be mounted in any position. If the circuit board slides out of snap track, a 
non-conductive “stop” may be required. Use only fingers to remove board from snap track. Slide out of 
snap track or push up against side of snap track and lift that side of the circuit board to remove. 

Do not flex 

board or use tools.

WIRING INSTRUCTIONS

PRECAUTIONS
•     Remove power before wiring. Never connect or disconnect wiring with power applied.
•    When using a shielded cable, ground the shield only at the controller end. Grounding both 
ends can cause a ground loop. 
•   It is recommended you use an isolated UL-listed class 2 transformer when powering the unit 
with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers may 
result in damage to any device powered by the shared transformer.
•    If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, or 
other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI 
Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC 
Transorb or diode, connects to the positive side of the power supply. Without these snubbers, 
coils produce very large voltage spikes when de-energizing that can cause malfunction or 
destruction of electronic circuits.
•    All wiring must comply with all local and National Electric Codes.

FIGURE 1: 

DIMENSIONS

INTERFACE SERIES

Installation & Operation Instructions

DMUX-8S

Phone:

 1-888-967-5224

Website:

 workaci.com

3.22"

(81.78mm)

4.82" (122.42mm)

L10

J10

J9

L9

J1

J4

J2

J3

L2

D2

K2

L1

D1

K1

L4

D4

K4

L3

D3

K3

= AUTO

A

= OFF

-

= ON

O

PULSE

TRIAC NORM

PWR

+

AC

-

DC

IN

+

-

M 1

POWER

D

E

3

O 2

C2

NC

NO

C1

NO

NC

A

O

A

O

NO

NC

C4

C3

NC

NO

A

O

A

O

3

3.25"

(82.55mm)

4.69" (119.13mm)

0.70” 

(17.78mm)

This program offers different modes of operation using the Solidyne™ fast pulse input.  Input ranges are 
given in percentages from 4-96% and also milliseconds from 10-230ms.  Relay action does not occur until 
receiving 10 identical cycles of the same range.  Any input range that is less than 4%, greater than 96%, or 
after 5 seconds with NO input pulse will command an ALL OFF relay action. 

Apply power: The “POWER” LED should light. Close the pulse input relay contacts: The “PULSE” LED should 
light indicating that the M978 is receiving the PWM signal. Further test the M978 operation by comparing 
the operation of output relays with respective input pulse. The LED for each relay will turn on when the 
respective relay is activated. No action on longer pulses.

SEQUENTIAL RELAY CONTROL

The program has to see 10 identical pulse cycles before a sequencing relay action can occur.

NOTE:

 <4%, >96%, or no pulse = ALL OFF

DIP SWITCH selections: OFF- 1, 3, 4 ON- 2 (only)

Summary of Contents for DMUX-8S

Page 1: ...t that side of the circuit board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with power applied When using a shielded cable ground the shield only at the controller end Grounding both ends can cause a ground loop It is recommended you use an isolated UL listed class 2 transformer when powering the unit with ...

Page 2: ...r until receiving 10 identical cycles of the same range Any input range that is less than 4 greater than 96 or after 5 seconds with NO input pulse will command an ALL OFF relay action Apply power The POWER LED should light Close the pulse input relay contacts The PULSE LED should light indicating that the M978 is receiving the PWM signal Further test the M978 operation by comparing the operation o...

Page 3: ...43 5 80 100 F 44 55 All OFF 110 130 DEADBAND 56 67 5 140 160 F 68 79 5 3 170 190 F H1 80 95 5 4 3 200 230 F H1 H2 ROOFTOP UNIT CONTROL This mode of operation is useful for 8 relay control of rooftop units Ten identical pulse cycles are needed to initiate an action and a 50 deadband is included Dip switch 1 when in the ON position at the 50 deadband range setting provides a fan override ON for a ti...

Page 4: ... Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C SENSOR NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Pulse Source Input Pulse Trigger Level Input Pulse Timing Off Time Between Pulses Digital Output Type Relay Contact Rating Relay Electrical Life Relay Mechanical L...

Reviews: