background image

S

ECTION

250

CONTINUED

F.

R

ELIEF

V

ALVES

(1)

The storage tank should be protected with a pressure (or combination temperature and pressure) relief valve set so as not to exceed the maximum 
tank operating pressure.  The relief valve should be located within 6" of the top of the tank.  Refer to local codes for the type of relief valve required.

(2)

Each heater should be protected with its own pressure relief valve.  The relief valve should be rated for the BTU/hr or LBS/hr of heater output.

(3)

The pressure relief valves and pressure relief elements of combination valves, when supplied, shall comply with applicable performance provisions of the
American National Standard for Relief Valves and Automatic Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22-1979.

(4)

Manually operate relief valves at least once a year.

(5)

If the temperature and pressure relief valve(s) on the appliance(s) discharge periodically, a problem exists and service to the water system is required. Periodic
discharge may be due to thermal expansion in a closed water system.

CAUTION!!!

To prevent scalding and/or personal injury, pipe outlet of relief valve(s)

to a floor drain with NO intervening valves or restrictions.

G. A

IR

E

LIMINATION

(A)

All of the air must be removed from the water piping in the system before the system will function properly.  Therefore, all high points in the system must be
vented or purged.  Relief valves may be used to purge air when they are at the high point.

(B)

If a water heater is installed in a closed water system, contact the water heater supplier or local plumbing inspector on methods to allow proper system expan-
sion.  A weeping pressure or temperature relief valve may be due to thermal expansion (i.e. expansion tanks) in a closed water system.  Do not plug the tem-
perature and pressure relief valve.

H. V

ENTING

S

YSTEM

(F

LUE

G

ASES

)

(1)

Vents for the heater(s) may be run individually or manifolded.  Two or more heaters may be vented through a common vent connector or manifold.  The common vent
connector or manifold shall be located at the highest level consistent with available head room or clearance to combustible material, and shall be sized in accordance with
approved engineering methods.  The area of the common vent connector or manifold shall not be less than the combined area of the individual draft hood outlets or the
individual vent connectors.

See the NATIONAL FUEL GAS CODE ANSI Z21.13-1984 Section 1.5 "Venting of Appliances" for more detailed information.

(2)

Only locally approved code type venting should be installed.

(3)

The draft hood furnished with each heater/boiler must be installed as shown on the hook-up diagram.

(4)

The sheet metal collar included with the heater musted be installed between the heater & the draft hood.

I.

G

AS

C

ONNECTION

(1)

The gas line should be a separate line running directly from the gas meter to the heater, unless the existing gas line is of ample capacity.  Verify the capacity of
the existing gas piping if it is to be used.

(2)

Install a union at the connection to the heater manifold.

(3)

Refer to the rating plate on the shell of the heater for proper gas manifold pressure.  The manifold pressure is measured downstream of the gas pressure regu-
lator.  Do not exceed the maximum gas pressure specified on the rating plate.

(4)

A trap (drip leg) must be installed upstream of the gas pressure regulator.

(5)

The heater must be disconnected from the gas supply piping system during any pressure testing of the gas supply piping.

(6)

Gas connections and heater should be properly tested for leaks before being put into operation.

(7)

Gas supply lines should be purged of air at the heater before startup.

(8)

The flow rate is determined by controls preset at the factory. There is no field adjustment for the minimum input rate.

J. T

ESTING

(1)

Your heater has been pressure tested in accordance with ASME CODE SECTION IV and fire tested in accordance with U.L. 795.

(2)

It is recommended that the heater and the system into which it is installed be tested before operating the system.  The exact nature of the test(s) are deter-
mined by the system's component(s), but will generally consist of a water pressure test and a gas leak test.  This testing should be completed as part of the
normal installation procedure by the installing company.

(3)

Once the entire installation is complete, the unit should have an operation test to insure that the ignition system safety shut of device works properly.
Instructions in the manufacturer's literature shall be followed in conducting this test.

K. M

AINTENANCE

CAUTION

The following inspections and tests should be performed

at regular intervals at least every three to six months.

Failure to do so may void your warranty.

(1)

Turn the Operating Thermostat and High Limit Aquastat down, then up until heater turns off and on to verify that the controls are operating satisfactorily.

(2)

Check the High Limit Aquastat Well for lime.  If 1/16" lime is deposited on the outside of the well, the coil needs to be delimed.

(3)

Inspect the coil and burner assembly to make sure that they are free from dust, lint, dirt, etc.  If they are dirty, remove all foreign material by washing, flushing,
or air cleaning, etc.

(4)

Inspect venting system to make sure that it is free of dirt and corrosion.

(5)

Make periodic visual checks of burners and pilot flames.

(6)

Check combustion air inlets in the room to see that they are clear of obstructions.

L. A

QUASTAT

I

NFORMATION

(1)

The Heater is equipped with two aquastats - a high limit safety aquastat in the upper (hot out) manifold and an operating aquastat (Thermostat ) in the lower
(tank water in) manifold.  The operating aquastat “Thermostat” should be set approximately 10°F lower than the desired tank tamperature setting.  

The HI limit

aquastat should be set at least 60°F higher than the thermostat setting.

For example: if desired water temperature in tank is 140°F  set the thermostat at

130° F and Hi limit at 200°F; for 150°F tank water temperature set the thermostat at 140°F and the Hi limit at 210°F. etc.  When 2 or more heaters are operated
together, set the 2nd heater thermostat 3° to 5° lower than the first heater thermostat and the third heater thermostat 3° to 5° lower than the 2nd heater thermo-
stat, etc.  Check the tank thermometer and correct thermostat so that the heater shuts off at desired tank water temperature.  
Note: tank aquastat may be used interchangeably with the heater operating aquastat. 

(2)

Water entering heater below 140 °F will cause the heater to condense, limiting its service life.

Summary of Contents for B Series

Page 1: ...al Designed and Manufactured in Accordance with ASME Code Section IV Heating Boilers E T L Listed ASME Code Construction and Stamped Photo shown may vary from actual model Model B_G Series Gas Fired C...

Page 2: ...site http www ajaxboiler com Email info ajaxboiler com Ace Boiler Inc formerly Ace Buehler Inc is a division of Ajax Boiler Inc ACE BOILER INC E T L Listed Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q Q...

Page 3: ...e the heater so that leakage from tank or connections will be directed to a floor drain and will not damage adjacent area or lower level floors 2 The minimum clearance between a heater and a storage t...

Page 4: ...is measured downstream of the gas pressure regu lator Do not exceed the maximum gas pressure specified on the rating plate 4 A trap drip leg must be installed upstream of the gas pressure regulator 5...

Page 5: ...P OP Check Valve Pressure Relief Valve Pressure Temp Gauge Primary Operational Aquastat Unit Circulation Pump System Recirculation Pump Check Valve Pilot Safety Relay Ground Hi Limit Aquastat Control...

Page 6: ...STANDARD FOR CSD 1 G 22225 N A HEADER COMB GAS VALVE SHUT OFF VALVE PILOT LINE PILOT LINE TYP COMB GAS VALVE TYP HEADER SHUT OFF VALVE B2 THRU B8 INDOOR OUTDOOR CSD 1 GAS TRAIN FOR MODELS B11 THRU B1...

Page 7: ......

Page 8: ...CONTROLS AND GAS TRAIN GAS FIRED COPPER FIN CONE COIL WATER HEATERS HEAVY DUTY INDUSTRIAL WATER HEATERS MINI PACK SEMI INSTANTANEOUS WATER HEATERS PACKAGED STORAGE WATER HEATERS CLEAN STEAM BOILERS AS...

Page 9: ...and accept the product when received as conforming to their purchase order specifications and approved drawings All claims for non conformance errors shortages etc must be made within 10 days after re...

Page 10: ...4 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com June 2010 Ace Heating Solutions LLC ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE...

Page 11: ...060 http www ajaxboiler com mail ajaxboiler com February 2007 ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230 FAX 714 540 2239 www aceheatingllc com Ace Heating Solu...

Page 12: ...anta Ana California 92704 United States Tel 714 437 9050 Fax 714 437 9060 http www ajaxboiler com mail ajaxboiler com ACE Heating Solutions LLC 2701 S HARBOR BLVD SANTA ANA CA 92704 PHONE 714 540 2230...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...es at very high temperatures insulation shielding and air circulation may be necessary to protect the controls Proper insulation or shielding should be provided by the appliance manufac turer make sur...

Page 17: ...o ground NOTE Earth ground is not required To connect the D80B follow the wiring diagrams sup plied with the vent damper or see Fig 8 for typical connec tions Connect Ignition Module 1 Connect remaini...

Page 18: ...T DAMPER PLUG OPT 5 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL Fig 2 S8610F H S8670D in a heating system with an atmospheric burner 5 TABLE 4 TERMINAL CROSS REFE...

Page 19: ...9 0523 MV MV PV PV GND BURNER 24V GND 24V TH W VENT DAMPER PLUG SPARK 5 S8610A B POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM C...

Page 20: ...TOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL PILOT BURNER GROUND PILOT GAS SUPPLY 9 69 0523 Fig 8 S8610F H S8670D in a heating system with an atmospheric burner and a D80B Vent Damper L...

Page 21: ...23 Fig 10 S8610F H S8670D in a hydronic heating system with a D80D Vent Damper 2 MV MV PV PV GND BURNER 24V GND 24V TH W OPT VENT DAMPER PLUG OPT SPARK 4 S8610F H S8670D POWER SUPPLY PROVIDE DISCONNEC...

Page 22: ...ne as described in Steps 1 and 5 below on initial installation and any time work is done involving the gas pip ing STEP 3 Reset the Module Turn the thermostat to its lowest setting Wait one minute As...

Page 23: ...burner igniter sensor and provide shield if necessary If flame rod or bracket are bent out of position restore to correct position STEP 3 Check spark ignition circuit You will need a short jumper wire...

Page 24: ...ing the pilot adjustment screw on the gas control clockwise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly...

Page 25: ...V PV MV PV MAIN VALVE PILOT VALVE TO 24V GND TO 24V 3 3 Fig 17 Representative schematic for S8610F H See Fig 1 for hookup S8670 is similar except the timing circuit includes a purge timer See Fig 6 fo...

Page 26: ...water pumps are in operating condition b Test low water cutoffs automatic feed water controls pressure and temperature limit control lers and relief valves in accordance with the manufacturer s recomm...

Page 27: ...ntrol after compression nut has been tightened because this can result in gas leakage at connection 2 Square off and remove burrs from end of tubing 3 Push tubing into compression nut clearance hole u...

Page 28: ...ot flame 6 Always replace pilot adjustment cover screw and tighten firmly after completing adjustment to assure pro per operation Service WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEV...

Page 29: ...e would result in personal injury and or loss of prop erty it is the responsibility of the installer to add devices safety limit controls that protect against or systems alarm supervisory systems that...

Page 30: ...llation and adjustment CAUTION Check the installation for no flow switch operation Make appropriate adjustments to the sensitivity adjustment screw to be sure the switch restores fully at the desired...

Page 31: ...ls The thermostat or the fuse will be damaged DO NOT allow any flame to impinge on the regulator vent tubing if sup plied It may clog and cause gas valve malfunction DO NOT use the gas cock to adjust...

Page 32: ...or 6 for a typical connection diagram X XX UL INSTALLATION INSTRUCTIONS U S Registered Trademark Copyright 1995 Honeywell Inc All Rights Reserved L4008A B E L L6008A G H Aquastat Controllers APPLICATI...

Page 33: ...R IGNITION TRANSFORMER RA89A RELAY RA817A PROTECTORELAY CONTROL BURNER MOTOR 24V THERMOSTAT 2 1 3 4 T T 1 2 3 4 M8785 Fig 5 Typical oil fired hydronic heating system with domestic hot water SETTING Co...

Page 34: ...9 mm OD for both inlet and outlet Approval CE 0063AU1215 U S Registered Trademark Copyright 2000 Honeywell Inc All Rights Reserved INSTALLATION INSTRUCTIONS 69 1225 4 VR8104 VR8204 and VR8304 Intermit...

Page 35: ...mine if the pressure regulator setting factory set will meet the appliance manifold requirements after conversion NOTE Convertible pressure regulator models suffix letter R do not have field adjustabl...

Page 36: ...BINATION GAS CONTROLS 5 69 1225 4 Fig 1 Top view of convertible pressure regulator cap Install Adapters To Control If adapters are being installed on the control mount them as follows Flanges 1 Choose...

Page 37: ...hanism to reduce the pilot flow if necessary If pilot adjustment is necessary proceed as follows 1 Remove pilot adjustment cover screw See Fig 6 2 The pilot adjustment is shipped at the full pilot gas...

Page 38: ...eter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOMETER Make sure the g...

Page 39: ...Non Regulating On Off U Models Non regulating VR8204U Valves are designed for application in various parts of Europe where a separate distinct pressure regulator is required The VR8204U is similar to...

Page 40: ...f heater falls off this is usually a sign of lime in the coil The ACE coil will bang or knock if lim ing condition is severely restricting circulation Customers have reported operating ACE heaters and...

Reviews: