ACE BOILER INC.
Page 21
Preventive Maintenance
Every 3 months:
1. Visually check for leaks at any joints, including the valve body, piping, and controls.
2. Visually check for corrosion on the control valve, pilot, bulb, and strainer.
3. Check for full valve shut-off. Refer to
Trouble Shooting section on
Page 18
.
4. Test the temperature hand-wheel and pressure screw for freedom of movement. Lubricate if
necessary.
5. Remove the temperature control bulb from the Mini-Pack and check for any corrosion or erosion.
Remove/clean any scale from bulb surface.
6. Strainers should be inspected and cleaned. Damaged screens should be replaced with same
mesh.
7. Check and tighten flange nuts as needed.
Annual Maintenance:
1. The relief valve must be tripped to insure proper operation as a safety device.
2. Pull the tube bundle and clean the inside and outside of the tube bundle of scale. The frequency of
tube cleaning will be determined after inspection. (Heavy scale will indicate that more frequent
cleaning is necessary). A light sludge or scale coating on the tube greatly reduces its effectiveness.
A marked increase in pressure drop and/or reduction in performance usually indicate cleaning is
necessary. The tube bundle should be cleaned with a tube brush and/or an acceptable cleaning
solution.
3. Check ALL operating components for proper functionality. Check all electrical connections.
Replacement Parts
Ace Boiler maintains a complete equipment list for each Mini-Pack, filed by serial number. In order for us
to give prompt service and to ensure that correct parts are supplied, please be sure and supply the model
and serial number.
Replacement parts may be ordered from directly from manufacturer.
Material Data Safety Sheets
Some of Ace products contain materials that have been recognized as posing health risks. Material
Safety Data Sheets for these materials are available from your local Manufacturer's rep. When
requesting this information, be sure to have the model number and serial number available.
If you do not know who your local Manufacturer's Rep is, you can find out by logging into the
www.ajaxboiler.com
website, and clicking on the Representative tab found in the table of contents.
Ajax Boiler Inc.
2701 S. Harbor Blvd.
Santa Ana, CA 92704
Parts: 714.437.9050
www.ajaxboiler.com
email: [email protected]
Ace Heating Solutions, LLC
2701 S. Harbor Blvd.
Santa Ana, CA 92704
PH: 714.540.2230: FAX: 714.540.2239
www.aceheatingllc.com
www.aceheatingllc.com
Summary of Contents for Mini-Pack
Page 2: ......
Page 6: ...ACE BOILER INC Page 5 Parts of the Mini Pack ...
Page 11: ...ACE BOILER INC Page 10 Installation Diagram Single Wall ...
Page 12: ...ACE BOILER INC Page 11 Installation Diagram Double Wall ...
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 98: ......
Page 99: ......