Internal Filter Maintenance

The unit will typically be provided with 2-inch 
thick pleated paper filters in the airstream. These 
filters should be checked according to a routine 
maintenance schedule and replaced as necessary 
to ensure proper airflow through the unit. See table 
below for pleated paper filter size and quantity for 
each unit. Replacement filters shall be of same 
performance and quality as factory installed filters. 
Filter must be pleated design with integral metal 
grid. Two acceptable filter replacements are Aerostat 
Series 400 or Farr 30/30

®

.

The standard 2-inch thick pleated paper filter is rated 
at MERV 8, but 2-inch thick MERV 13 filters can be 
substituted, if desired.

Filter Size (Quantities)

Model

2-inch  

aluminum mesh  

(weatherhood)

2- and 4-inch 

pleated filters

MPX-H14

20 x 25 (2)

20 x 25 (2)

MPX-H24

16 x 25 (4)

20 x 25 (4)

MPX-H34

20 x 25 (4)

16 x 25 (6)

WARNING

REFER TO GENERAL SAFETY INFORMATION

Do not operate this unit without the filters and 
birdscreen installed. They prevent the entry of 
foreign objects such as leaves, birds, etc. 

Do not remove access panels or other unit 
components while standing on a ladder or other 
unsteady base. Access panels and unit components 
are heavy and serious injury may occur.

Coil Maintenance

Coils must be cleaned to maintain maximum 
performance. Check coils once per year under normal 
operating conditions and if dirty, brush or vacuum 
clean. Soiled fins reduce the capacity of the coil, 
demand more energy from the fan and create an 
environment for odor and bacteria to grow and spread 
through the conditioned zone. High pressure water 
(700 psi or less) may be used to clean coils with a 
fin thickness over 0.0095 inches thick. TEST THE 
SPRAY PRESSURE over a small corner of the coil to 
determine if the fins will withstand the spray pressure.

For coils with fragile fins or high fin density, foaming 
chemical sprays and washes are available. Many coil 
cleaners use harsh chemicals, so they must be used 
with caution by qualified personnel only. Care must be 
taken not to damage the coils, including the fins, while 
cleaning. 

Caution: Fin edges are sharp!

Drain pans in any air conditioning unit will have 
some moisture in them, therefore, algae and other 
organisms will grow due to airborne spores and 
bacteria. Periodic cleaning is necessary to prevent 
this buildup from plugging the drain and causing the 
drain pan to overflow. Inspect twice a year to avoid 
the possibility of overflow. Also, drain pans should be 
kept clean to prevent the spread of disease. Cleaning 
should be performed by qualified personnel.

External Filter Maintenance

Aluminum mesh, 2-inch thick 
filters are located in the supply 
weatherhood (if the weatherhood 
option was purchased). These 
filters should be checked and 
cleaned on a regular basis for 
best efficiency. The frequency 
of cleaning depends upon the 
cleanliness of the incoming air. 
These filters should be cleaned by rinsing with a mild 
detergent in warm water prior to start-up.

Filter

Outdoor Air Intake Hood  

Mesh Filter Access

Outdoor Air Filters:  

Access to the outdoor air filters is 

through the door labeled “Filter Access” on the access side 
of the unit.

Refer to Access Door Descriptions section of this manual for 
additional information on filter locations and access.

WARNING

Biological hazard. May cause disease. Cleaning 
should be performed by qualified personnel.

38

Model MPX Make-Up Air Unit

Model XMPX Make-Up Air Unit

Summary of Contents for XMPX Series

Page 1: ...r seismic activity are present If more information is needed contact a licensed professional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Elect...

Page 2: ...ed to be taken to prevent deterioration of the unit during storage The user assumes responsibility of the unit and accessories during storage The manufacturer will not be responsible for damage during...

Page 3: ...Center Components DDC Control Package 12 Digital Scroll Compressor Controller 12 Fan Proving Switch 12 Variable Frequency Drives VFD 13 Phase Monitor 13 Typical Wiring Diagram 14 15 Controller Sequenc...

Page 4: ...Operation and Maintenance manuals for additional information Plenum and Plug Indirect Gas Fired Furnace Model PVF PCO3 Controller MPX Subassemblies Blower Each unit has just one backward curved blowe...

Page 5: ...ATER 4 INCH FILTERS I H MPX H34 Unit Size Dimensions MPX H14 MPX H24 MPX H34 MPX H34 Furnaces Single Furnace Double Furnace A 54 3 67 2 72 2 76 2 B 86 6 96 7 97 7 97 7 C 34 0 36 4 33 2 33 2 D 48 1 58...

Page 6: ...mage from occurring to the refrigerant system This unit contains a system that is pressurized with refrigerant and if it is damaged the refrigerant could leak into the atmosphere or cause bodily harm...

Page 7: ...be level Shim as required to level 3 Install Ductwork Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines Duct adapter provided to support ducts prior to setting the...

Page 8: ...rovided with the P trap If local and area building codes permit the condensate may be drained from the P trap onto the roof but a drip pad should be provided beneath the outlet If local and area codes...

Page 9: ...o overheat and eventually fail Maximum allowable imbalance is 2 To determine voltage imbalance use recorded voltage measurements in this formula Low Voltage Controller Circuitry Manufacturer recommend...

Page 10: ...e Air Temperature Sensor All units are supplied with a Discharge Air Temperature Sensor that is to be eld installed prior to unit start up The sensor is to be installed at least three duct diameters d...

Page 11: ...use Blocks 10 Step Down Transformers number varies Low Voltage Side 11 DDC Controller 12 Relays 13 Fan Proving Switch Dirty Filter Switch on side wall 14 Low Voltage Terminal Strip 15 Hot Gas Reheat C...

Page 12: ...ch The unit uses a pressure switch to prove fan operation before operating any heating or cooling sequence It does this by verifying a difference in air pressure on both sides of the air supply fan Wh...

Page 13: ...ed sensors and controlling devices such as CO2 sensors dehumidistats or pressure sensors Refer to the VFD manufacturer s information and unit speci c wiring diagram supplied with the unit For addition...

Page 14: ...R R7 21 24 12 FPS NO C 90 NO3 OAI OAD ACC W BL Y PK Y BL W PK BL R 111 112 SUPPLY FAN M MAIN POWER TO UNIT GROUND L1 L2 L3 DB1 DS1 Y Y PM T1 T2 T3 PM C OUT DL1 4 D1 S4 S6 Y 1 2 ST1 O L 95 96 ST1 A2 A...

Page 15: ...RESSOR RELAY CIRCUIT B R7 COMPRESSOR INTERLOCK RELAY CIRCUIT A R8 COMPRESSOR INTERLOCK RELAY CIRCUIT B RBV REHEAT VALVE CONDENSER RH HEAT RELAY RHV REHEAT VALVE HOT GAS REHEAT S1 EXHAUST SWITCH S3 SUP...

Page 16: ...ehumidi cation Sequence The cooling is controlled to maintain the cooling coil set point The dehumidi cation sequence will be locked out when the OA is less than 10 F above the cold coil set point The...

Page 17: ...the proving switch on the supply air blower and displays an alarm in case of blower failure DX Alarm The DDC monitors the refrigerant pressure and shuts off the refrigeration circuit in the case of hi...

Page 18: ...to enable or disable speci c functions of the unit A unit speci c wiring diagram is included with each panel If speci ed by the owner the remote panel may have a Remote Interface factory installed ins...

Page 19: ...Coil M 1 2 3 4 13 5 12 9 11 13 10 8 13 14 7 15 6 Service Valve for Subcooling Gauge High Side Pressure Drop Circuit A Pressure Port for Troubleshooting Valve Service Valve for Superheat and Low Side P...

Page 20: ...le but excessive bubbles may indicate improper charge or a leak in the system A green dot means that moisture is below a safe operation level in the refrigerant while a yellow dot indicates moisture h...

Page 21: ...n system is excessive cycling on and off The digital scroll compressor eliminates excessive cycling by allowing the compressor to continue to run but internal compression is eliminated in brief cycles...

Page 22: ...Once the call for cooling exceeds 70 then the digital scroll will begin running again in conjunction with the xed scroll compressor see below System Start Up During unit start up amperage draw readin...

Page 23: ...l mode during start up Use necessary precautions to avoid injury All data must be collected while the unit is running In order to measure volts and amps the control center door must be open and the un...

Page 24: ...e Yes No If bubbles are visible in sight glass stop the start up process Refrigerant charge may not be adequate Consult factory Color of Center Dot Green Yellow Hot Gas Bypass Operational Yes No Not p...

Page 25: ...which may cause personal injury or failure of the following components Fan Shaft Bearings Motor Fan Wheel Belt Tighten all fasteners and set screws securely and realign drive pulleys after adjustment...

Page 26: ...cess doors open or without proper ductwork in place as the fan motors will overload Vibration Excessive vibration may be experienced during initial start up Left unchecked excessive vibration can caus...

Page 27: ...low prior to contacting the factory please determine the following information Air ow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with S...

Page 28: ...FD to regulate fan speed in response to various optional sensors such as dehumidistats pressure sensors or CO2 sensors These may be factory installed or they may be provided and installed by the owner...

Page 29: ...t Check motor wiring Check motor nameplate versus supplied voltage Motor horsepower too low See speci cations and catalog for fan curves to determine if horsepower is suf cient Shorted windings in mot...

Page 30: ...a 1 64 inch de ection per foot of span between sheaves Worn belt Replace Motor base or blower loose Tighten mounting bolts Bearing and drive misaligned Realign Noise being transmitted by duct Make sur...

Page 31: ...ine voltage Check line voltage If more than 10 from compressor marking correcting is necessary Compressor motor protector open Motor thermal protector automatically resets Allow time 2 hours for compr...

Page 32: ...erload If compressor is hot allow compressor to cool for two hours Recheck for open circuit Improper refrigerant charge Check subcooling Improperly wired Review wiring schematics Loose wiring Check al...

Page 33: ...ove non condensable from system Dirty condenser coil Clean condenser coil Condenser fan not running or running backwards Check electrical circuit and fuse Check fan cycling controls High load conditio...

Page 34: ...n oversized Contact factory Compressor loses oil Refrigerant leak Check system for leaks Repair leaks and add refrigerant Short cycling Check low pressure control settings Refrigerant ood back Check t...

Page 35: ...air ow Check air ow check lters check drive for loose parts or belts Malfunctioning or defective expansion valve Check bulb of thermal expansion valve Frost on evaporator coil Hot gas bypass valve not...

Page 36: ...ess panels and unit components can be heavy and serious injury may occur This unit requires minimal maintenance to operate properly To ensure proper operation and longevity the following items should...

Page 37: ...ted and require no further lubrication under normal use Normal use being considered 20 F to 120 F and in a relatively clean environment Some bearings are relubricatable and will need to be re greased...

Page 38: ...less may be used to clean coils with a n thickness over 0 0095 inches thick TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the ns will withstand the spray pressure For coils...

Page 39: ...____________________________ _________________________________________________ Date __________________ Time _____________ AM PM Notes ___________________________________________ ______________________...

Page 40: ...transportation prepaid Motors are warranted by the motor manufacturer for a period of one year Should motors furnished by Accurex prove defective during this period they should be returned to the nea...

Reviews: