AC Pro ACAT24F/NaA Owner'S Manual Download Page 1

Owner's Manual 

Original 

Instructions 

Air 

Conditioners 

A-Coils

Models: 

ACAT24F/NaA 

A

CAT36F/NaA 

ACAT48H/NaA

A

CAT60H/NaA 

Summary of Contents for ACAT24F/NaA

Page 1: ...Owner s Manual Original Instructions Air Conditioners A Coils Models ACAT24F NaA ACAT36F NaA ACAT48H NaA ACAT60H NaA ...

Page 2: ...gize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual using environment otherwise it may impact the using convenience 4 This product has gone through strict inspection and operational test before leaving the factory In order to avoid damage due to improper disassembly and inspection which may impact the normal operation of unit please do not ...

Page 3: ...s when personal injury or property loss is caused by the following reasons 1 Damage the product due to improper use or misuse of the product 2 Alter change maintain or use the product with other equipment without abiding by the instruction manual of manufacturer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation...

Page 4: ... 4 Installation 4 4 1 Pre Installation Instruction 4 4 2 Location 5 4 3 Piping Work 5 4 4 Condensate Removal 6 4 5 Ductwork 7 4 6 Unit Installation 8 4 7 Sealing Ducts 8 4 8 Leak Testing Evacuating and Charging 8 5 Blower Speed Selection 9 6 Maintenance and Care 9 6 1 Drain Pipe 9 6 2 Notice before Seasonal Use 9 6 3 Maintenance after Seasonal Use 9 6 4 Parts Replacement 9 7 After Sales Service 10...

Page 5: ...ith the kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and National Electrical Code NEC for special require...

Page 6: ...cal equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves and protective clothing 2 Product Introduction 2 1 Product Description The AC PRO A Coil offers the perfect combination of superior product quality operating efficiency operating sound levels and value for money The evaporator unit uses the environmentally friend...

Page 7: ...A Coils 3 2 3 Physical Dimension Unit inch Model Dimension W D H A B ACAT24 36 17 1 2 21 1 4 23 15 7 8 19 3 8 ACAT48 60 24 1 2 21 1 4 28 1 2 22 7 8 19 3 8 2 4 Names of Main Parts ...

Page 8: ...sers and line sets 4 Installation 4 1 Pre Installation Instruction 4 1 1 Checking Product Received After receiving the product please check if there is any damage caused by transportation Shipping damage is the responsibility of the carrier Verify the model number specifications and accessories are correct prior to installation The distributor or manufacturer will not accept claims from dealers fo...

Page 9: ...oil is designed for indoor installation only Do not install it outdoors When installing the coil take consideration to minimize the length of refrigerant tubing as much as possible Do not install the air handler in a location either above or below the condenser that violates the instructions provided with the condenser Service clearance is to take precedence Allow a minimum of 24 in front of the u...

Page 10: ... m Φ1 4 15 30 Φ3 8 35 40 Φ1 2 45 50 Φ5 8 60 65 Φ3 4 70 75 Φ7 8 80 85 4 4 Condensate Removal 1 It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or corrupt the unit 2 It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water fro...

Page 11: ...designed for a complete supply and return ductwork system Do not operate the unit without all ductwork completed Do not operate this product without all ductwork attached Inadequate ductwork that restricts airflow can result in improper performance and compressor or heater failure Ductwork is to be constructed in a manner that limits restrictions and maintains suitable air velocity Ductwork is to ...

Page 12: ... be an airtight seal between the bottom of the furnace and the return air plenum Use fiberglass sealing strips caulking or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal Return air must not be drawn from a room where the air handler or any gas fueled appliance i e water heater or carbon monoxide producing device i e wood fireplace is installed Ensur...

Page 13: ...ich will prolong the unit life span 6 1 Drain Pipe Regularly check if the drain pipe is clogged in order to drain condensate smoothly 6 2 Notice before Seasonal Use 1 Check if the inlet outlet of the indoor unit is clogged 2 Check if the filter screen has been set soundly 3 Check if the unit is installed firmly If there is something abnormal please contact the local appointed service center 6 3 Ma...

Page 14: ...nated by factory Warranty should meet the following requirements 1 First run of the unit should be operated by professional personnel from factory appointed service center 2 Only factory manufactured accessories can be used on the machine 3 All the instructions listed in this manual should be followed 4 Warranty will be automatically invalid if fails to obey any item mentioned above ...

Page 15: ......