25
Alarm lines (eight monitored analogue inputs)
The AZWG10200-PSTN/IP CONVERTER has eight analogue inputs that are
freely configurable for EN 54-21 fire and fault notifications or multiple
breaking and entering and technical notifications. The following settings
can be configured for each input:
wiring, input type; the following options are available for
this:
o
Not active: input is switched off
o
Normally Open: input is normally open, operating
current (NO)
o
Normally Closed: input is normally closed, standby
current (NC)
o
10K monitored: input is monitored via 10KΩ in
normal state
o
Double resistance monitored: monitored with double
resistance; 8K2 in normal state, 23K2 in alarm state,
opened or short-circuited in the event of tampering
o
Siemens FAC N.O.: configuration for normally open
contact of a Siemens fire alarm system
o
Siemens FAC N.C.: configuration for normally closed
contact of a Siemens fire alarm system
o
Bosch FAC N.C. fire: configuration for normally closed
contact of a BOSCH fire alarm system and fire
notification
o
Bosch FAC N.C. error: configuration for normally
closed contact of a BOSCH fire alarm system and
error notification.
Delay in hours, minutes and seconds: if the input resets
back to normal state within the set delay time, no
notification is issued.
Sequence: notifications are handled/processed as per the
sequence set in the 'Transmission' tab.
Alarm: as soon as the input is enabled.
Reset: as soon as the input is reset to normal state. If 'No
reporting' is set, this notification is not sent.
Area: notification partition.
Text: free text field with 16 characters. This text is sent
when the inputs go into 'Alarm' and 'Reset' states. Use only
characters A to Z, 0 to 9 and do not use bookmarks or
international characters.
The selected protocol coding for the line notification is displayed in the
window
below.
Summary of Contents for AZWG10200
Page 1: ...AZWG10200 Version 1 8 6 6 AZWG10200 ABUS PSTN IP converter EN ...
Page 14: ......
Page 16: ......
Page 31: ...31 Diagnosis Modules ...
Page 40: ...Notes ...