background image

Calibration

Input and output ranges as specified on your order are factory 
pre-configured (at 24°C ±1°C). Top-mounted, Zero and Span 
potentiometers can be used to calibrate the output to compen-
sate for load and lead variations.
1.  Apply power to the module and allow a minimum 20 minute 

warm up time.

2. Using an accurate calibration source, provide an input to 

the module equal to the minimum input required for the 
application.

3. Using an accurate measurement device for the output, 

adjust the Zero potentiometer for the exact minimum output 
desired. The Zero control should only be adjusted when the 
input signal is at its minimum. This will produce the cor-
responding minimum output signal.  For example: 4 mA for 
a 4-20 mA output or –10 V for a ±10V output.

4.  Next, set the input at maximum, then adjust the Span pot for 

the exact maximum output desired. The Span control should 
only be adjusted when the input signal is at its maximum. 
This will produce the corresponding maximum output 
signal. Example: for 4-20 mA output, the Span control will 
provide adjustment for the 20 mA or high end of the signal.

5.  Repeat adjustments for maximum accuracy.

Output Test Function

The test button may be used to drive the device on the output 
(a panel meter, chart recorder, etc.) with a known good signal 
that can be used as a system diagnostic aid during initial start-
up or during troubleshooting. 
When depressed it will drive the output with a known good 
signal. When released, the output will return to normal.
The Test Range potentiometer is factory adjusted to approxi-
mately 50% of the output span. It can be field adjusted if 
required.
Press and hold the Test button and adjust the potentiometer 
for the desired output level. When released, the output will 
return to normal.

Operation

The API 4400 G through API 4408 G are factory configured 
series to your exact input and output requirements. 
Up to four inputs can be scaled and connected to either addi-
tive or subtractive amplifier inputs according to the model 
designation.
The input signal is filtered, and cancels any offset of the input 
relative to the output. 50 

 shunts are used at the input for 

current-to-voltage conversion if required.
The green LoopTracker

®

 input LED provides a visual indication 

that a signal is being sensed by the input circuitry of the mod-
ule. It also indicates the input signal strength by changing in 
intensity as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as 
the process changes, check the module power or signal input 
wiring. Note that it may be difficult to see the LEDs under bright 
lighting conditions.
The red LoopTracker output LED provides a visual indication 
that the output signal is functioning. It becomes brighter as 
the input and the corresponding output change from minimum 
to maximum. 
For current outputs, the red LED will only light if the output loop 
current path is complete. For either current or voltage outputs, 
failure to illuminate or a failure to change in intensity as the 
process changes may indicate a problem with the module 
power or signal output wiring. 

Precautions

WARNING! All wiring must be performed by a qualified electri-
cian or instrumentation engineer. See diagram for terminal 
designations and wiring examples. Consult factory for assis-
tance. 

WARNING! Avoid shock hazards! Turn signal input, output, and 

power off before connecting or disconnecting wiring, or removing 

or installing module.

Précautions

ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de 
câblage. Consulter l’usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal 
d’entrée, le signal de sortie et l’alimentation électrique avant 
de connecter ou de déconnecter le câblage, ou de retirer ou 
d’installer le module. 

Socket and Mounting

Install module in a protective panel or enclosure. Allow space 
around module for air flow. Use API 011 or API 011 FS socket. 
See specifications for maximum allowable socket voltages. The 
socket clips to a standard 35 mm DIN rail or can be mounted to 
a flat surface.

Ranges

See the model/serial number label for module information, 
module power requirements, options, and I/O range informa-
tion. 
API 4400 G through API 4408 G input and output ranges are 
factory configured as indicated on the serial number label.

Signal Inputs

Polarity must be observed when connecting the signal input.
Terminals 4, 5, 6, 7, 8 provide the appropriate connections for 
the input signal. Polarity must be observed when connecting 
the signal input. 
The negative (–) connection for all inputs is connected to 
terminal 5. 
The positive (+) connection for input A is to terminal 4.
The positive (+) connection for input B is to terminal 6.
The positive (+) connection for input C is to terminal 7.
The positive (+) connection for input D is to terminal 8.

Signal Output

Polarity must be observed for output wiring connections. If the 
output does not function, check wiring and polarity.
When a current output is ordered, it provides power to the 
output current loop (sourcing).
Terminals 9 (+) and 10 (–) provide the connections for the 
output. Note that the output provides power to the output loop.

Module Power

Check model/serial number label for module operating voltage 
to make sure it matches available power.
AC power is connected to terminals 1 and 3. 
For DC powered modules (D option), polarity MUST be observed. 
Positive (+) is wired to terminal 1
Negative (–) is wired to terminal 3.

Installation and Setup 

API 4400 G through API 4408 G

API 011 

11-Pin Socket 

300 V Rating

TERMINAL LOCATION

TOP VIEW

8

7

6

5

4

9

10

11

1

2

3

0.312 [7.92] 

TYP.

2.060 [52.32]

0.165 

[4.19] 

TYP.

2.035 

[51.69]

0.594 

[15.08]

0.770 

[19.56]

2

1

3

4

5

6

7

8

9

10

0.970 

[24.64]

2.332 [59.22]

11

1.018 

[25.84]

API 011 FS 

11-Pin Finger 

Safe Socket 

300 V Rating

0.126 

[3.20] 

DIA. 

TYP.

1.181 [30.00]

0.220 [5.60]

1.496 [38.00]

TERMINAL LOCATION

TOP VIEW

8

7 6 5

4

9

10

11

1 2

3

1.063 

[27.00]

8

7 6 5

4

9

10

11

1

2

3

2.559 

[65.00]

0.925 

[23.50]

Input 

Common

3

2

1

11

10

9

8

7

6

5

4

PLC,  

Display, 

Recorder

Power  

AC or  

DC– 

Power  

AC or  

DC+

 

(+)

  (–)

Output

Module 

power

20 V loop 

power with 

mA output 

version

Socket  

top view

Key down 

when panel 

mounting

A

B

C

D

Input 

A

Input 

B

Input 

C

Input 

D

+

+

+

+

api-usa.com

1220 American Way Libertyville, IL 60048 
Phone: 

800-942-0315

 

Fax: 800-949-7502

A

BSOLUTE

 P

ROCESS

 I

NSTRUMENTS

API maintains a constant effort to upgrade and improve its products. 

Specifications are subject to change without notice. See api-usa.com for 

latest product information. Consult factory for your specific requirements.

WARNING:

 This product can expose you to chemicals includ-

ing lead and nickel, which are known to the State of California 

to cause cancer or birth defects or other reproductive harm. 

For more information go to www.P65Warnings.ca.gov

To maintain full isola-

tion avoid combining 

power supplies in 

common with input, 

output, or unit power.

 * Do not make 

connections to 

unused terminals!

Reviews: